| Plan Review Notes For Permit 05110699 |
| Permit Number |
05110699 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-06 00:00:00 | THE FOLLOWING MUST MEET THE MINIMUM | | | REQUIREMENTS AS PER THE FLORIDA BUILDING | | | CODE 2004: | | | | | | ACCESSIBILITY: | | | A)SECTION 11-1.2 | | | B)SECTION 11-5.2/5.3:SERVICE | | | COUNTERS/BARS:MAXIMUM HEIGHT 34" | | | C)SECTION | | | 11.5.6/11-4.2.5:TABLEWARE/CONDIMENT | | | AREAS AND MAXIMUM REACH DISTANCE. | | | | | | EGRESS REQUIREMENTS: | | | AS PER SECTION 812.3.1. | | | | | | INTERIOR FINISHES: | | | INTERIOR FINISHES MAY BE CLASS C AS | | | PER SECTION/TABLE 803.5 | | | | | | OCCUPANCY CHANGE: | | | A)SECTION 801.2/812.3.1:MUST MEET THE | | | MINIMUM REQUIREMENTS OF THE FOLLOWING: | | | A)MEANS OF EGRESS CAPACITY | | | B)INTERIOR WALL/CEILING FINISHES | | | C)FLORIDA FIRE PREVENTION CODE | | | | | | OCCUPANCY SEPARATION: | | | A)NOT REQUIRED AS PER TABLE 302.3.2.B |
|