| 2006-01-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | 1. SHTS L100 THRU L700 AND IR100 & IR500 |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | FOR THE LANDSCAPE ARCHITECT BUSINESS IS |
| | REQUIRED IN THE TITLE BLOCK OF EACH |
| | SHEET. FAC T1G1-16.004(2) & FS 481.319. |
| | 3. SHT A-401 ACCESSIBLE TOILET ROOM |
| | DETAIL. THE FOLLOWING INFORMATION IS |
| | REQUIRED TO SHOW COMPLIANCE WITH CHAPTER |
| | 11: |
| | FOR LAVS: |
| | A. 11-4.19.2 CLEARANCES |
| | C. 11-4.19.5 FAUCETS |
| | 6. SHT P-401 FLOOR SINK OR HUB DRAIN IS |
| | REQUIRED FOR THE ICE MACHINE. SECTION |
| | 802.1 - (FLOOR DRAINS ARE NOT APPROVED |
| | INDIRECT WASTE RECEPTORS). |
| | 10. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMITS. (NATURAL |
| | FOR THE STRUCTURE, AND LP FOR THE |
| | GENERATOR): |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - NOT ALL LENGTHS FOR |
| | EACH SECTION SHOWN. - STILL MISSING SOME |
| | LENGTHS FOR CUT SECTIONS. (NEW COMMENT - |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| | PLAN IN SOME AREAS). |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - TOTAL CONNECTED CAPACITY IS |
| | INDICATED AS 698,000 CFH. PLEASE |
| | CLARIFY. SECTION 106.1.1. - THIS STILL |
| | ADDS UP TO A DIFFERENT NUMBER (634,000 |
| | BTU'S). |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - ADDING UP |
| | MEASUREMENTS SUBMITTED ON GAS RISER |
| | DIAGRAM, THE TOTAL DEVELOPED LENGTH IS |
| | CLOSE TO 200FT. PLEASE RECHECK LENGTH TO |
| | THE MOST REMOTE OUTLET. - THIS HAS NOT |
| | BEEN ADDRESSED. |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. - INDICATE CUBIC |
| | FEET OF THE ROOM THE GAS DRYER IS IN TO |
| | DETERMINE IF IT IS IN A CONFINED SPACE. |
| | - NOT ADDRESSED. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | ****************NEW COMMENTS************ |
| | 1B. PIPE SIZING FOR GAS ISOMETRIC DOES |
| | NOT REFLECT THE TABLE FOR SEMIRIGID |
| | COPPER TUBING (402.4(8)). PLEASE RECHECK |
| | PIPE SIZES. |
| | 2B. PROVIDE AN APPROVED TABLE FOR 5.0 |
| | PSI FOR POLYETHYLENE TUBING FOR SYSTEM |
| | TO THE GENERATOR. TOTAL DISTANCE OF 200' |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |