| 2006-02-08 00:00:00 | PROVISO:2004 FLORIDA BUILDING CODE | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD & | | | FIRE SUPPRESSION.PLEASE PROVIDE | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION.PLEASE NOTE THE LOCATION | | | FOR KITCHEN EXHAUST FAN IN RELATION TO | | | THE PATIO WALL & OPENING.PER 2004 FMC | | | 506.3.12.2, SUCH TERMINATIONS SHALL NOT | | | CREATE A FIRE HAZARD OR TERMINATE LESS | | | THAN 10 FT FROM PARTS OF THE SAME OR | | | CONTIGUOUS BUILDING. | | | | | | IF YOU HAVE ANU QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|