| 2005-11-28 00:00:00 | DENIED:PLAN CHECK ONLY / 2004 FBC |
| | 1.PLAN SHEET M-101 & M-601, EF-1 & 2 |
| | LOCATED IN THE APPARATUS BAY.EQUIPMENT |
| | SCHEDULE INDICATES THE FANS ARE |
| | INTERLOCKED WITH THE BAY DOORS.PLEASE |
| | CLARIFY VENTILATION WHEN THE GARAGE |
| | DOORS ARE CLOSED. |
| | |
| | 2.O.A. CALCULATIONS WERE PROVIDED FOR |
| | ALL AREAS EXCEPT THE APPARATUS BAY. |
| | PLEASE PROVIDE CALCULATIONS IN |
| | ACCORDANCE WITH 2004 FMC 404.2.PLEASE |
| | NOTE, ADJOINING AREAS THAT CONNECT TO |
| | THE APPARATUS BAY SHALL BE MAINTAINED AT |
| | A POSITIVE PRESSURE PER 404.3. |
| | |
| | 3.PLEAES INDICATE IF THE CO SENSOR |
| | WILL BE TIED INTO EF-1 & 2. |
| | |
| | 4.ADDITIONAL PERMITS REQUIRED FOR THE |
| | HOOD & FIRE SUPPRESSION.PLEASE PROVIDE |
| | MANUFACTURERS SUBMITTAL DATA & PLANS |
| | WITH PERMIT APPLICATION.PLEASE |
| | INDICATE CLEARANCES TO COMBUSTIBLES PER |
| | 2004 FMC 506.3.7. |
| | |
| | 5.PLEASE PROVIDE MANUFACTURERS |
| | SUBMITTAL DATA FOR THE GAS GRILL LOCATED |
| | UNDER THE COVERED PATIO. |
| | |
| | 6.PLEASE CLARIFY CALCULATIONS FOR THE |
| | DECONTAMINATION ROOM.DO THEY INCLUDE |
| | COMBUSTION AIR? |
| | |
| | 7.PLAN SHEET E-100 INDICATES PROPANE |
| | TANK & EMERGENCY GENERATOR.PLEASE |
| | PROVIDE MANUFACTURE SUBMITTAL DATA. |
| | PROVIDE CAPACITY OF THE PROPANE TANK. |
| | INDICATE ABOVE GROUND OR UNDERGROUND |
| | INSTALLATION.PROVIDE DISTANCES TO |
| | PROPERTY LINES, BUILDINGS, ETC.SHOW |
| | COMPLIANCE WITH NFPA 58-102. |
| | |