| 2005-11-29 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE GROUNDING ELECTRODE SYSTEM MUST |
| | COMPLY WITH ARTICLE 250.50, EACH ITEM IN |
| | 250.52(A)(1) THROUGH(A)(6) MUST BE USED. |
| | INDICATE WHICH ARE AVAILABLE ON THE |
| | RISER DIAGRAM THAT PRESENTLY ONLY SHOWS |
| | A GROUND ROD AND WATER PIPE. ALSO VERIFY |
| | THAT THE WATER PIPE IS METAL AND NOT |
| | PVC. |
| | |
| | 2} THE #2 GROUNDING ELECTRODE CONDUCTOR |
| | IS NOT COMPLIANT PER 250.66. #1/0 |
| | MINIMUM IS REQUIRED. SEE ARTICLE. |
| | CORELATE SHEET E-501 WHICH SHOW A 4/0 |
| | DELTA GROUND. |
| | |
| | 3} THE RISER INDICATES 3#500(ASSUME |
| | UNGROUNDED CONDUCTORS) AND A #2 GROUND |
| | FROM THE FIRST DISCONNECT TO THE ATS AND |
| | ON TO THE MDP. THE GROUNDED CONDUCTOR IS |
| | NOT SHOWN. ALSO TO THE MDP. |
| | |
| | 4} THE GROUNDING SYMBOL AT THE GENERATOR |
| | INDICATE A GROUNDED NEUTRAL. IS THIS |
| | INTENDED TO OPERATE AS A SEPERATELY |
| | DERIVED SYSTEM? THE ATS DOES NOT |
| | INDICATE WHETHER IT IS A 3 OR 4 POLE. |
| | |
| | 5} THE GENERATOR FEEDERS TO THE ATS DO |
| | NOT INDICATE A NEUTRAL. SAME COMMENT AS |
| | #3. |
| | |
| | 6} PLEASE CHECK THE MANUFACTURERS |
| | NAMEPLATE RATING AGAINST THE500 MCM |
| | FEEDERS, SEE 445.13@115%. |
| | |
| | 7} SUPPLY MANUFACTURERS SPECIFICATIONS |
| | FOR THE GENERATOR AND ATS. |
| | |
| | 8} PLEASE PROVIDE A PANEL SCHEDULE FOR |
| | MDP AND DP1. |
| | |
| | 9} PLEASE INDICATE THE CIRCUIT NUMBERS |
| | FOR THE EQUIPMENT AT THE EQUIPMENT |
| | LOCATION ON THE PLAN, SEE CU'S ON SHEET |
| | E-120, WH, OVERHEAD DOORS ETC. |
| | |
| | 10} PLEASE COMPLY WITH 210.8(B)(3), SEE |
| | KITCHEN COUNTERTOPS. |
| | |