| Plan Review Notes For Permit 05110636 |
| Permit Number |
05110636 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-04-20 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THERE HAS BEEN A PANEL ADDED TO THE | | | SERVICE EQUIPMENT. PLEASE SUBMIT A RISER | | | DIAGRAM SHOWING ALL SERVICE EQUIPMENT | | | AND GROUNDING SYSTEM. ALSO PLEASE SHOW | | | THE LOCATION OF THE EQUIPMENT ON THE | | | PLAN.215.5 | | | | | | 2} THE NEW PORCH NEEDS A RECEPTACLE | | | ADDED TO COMPLY WITH 210.52(A)(1), SEE | | | REVIEWED PLAN. | | | | | | 3} THE NUMBER OF THE SHEET ON THE PLAN | | | SUBMITTED FOR REVISION DOES NOT MATCH | | | ANY SHEETS PREVIOUSLY SUBMITTED. PLEASE | | | CHANGE THE NUMBER TO REFLECT SHEET BEING | | | REVISED. | | | | | | 4} PLEASE PROVIDE A PANEL SCHEDULE FOR | | | THE NEW PANEL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|