| Plan Review Notes For Permit 05110633 |
| Permit Number |
05110633 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-09-07 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THERE ARE NEW APPLIANCES IN THE | | | KITCHEN ( ICE MAKER, WINE COOLER) THAT | | | AREN'T LISTED IN THE LOAD CALCULATION OR | | | ON THE PANEL SCHEDULE. ALSO THE | | | DISHWASHER AND DISPOSAL, ALTHOUGH | | | EXISTING, NUST BE INCLUDED. ALL LOADS | | | MUST BE CALCULATED TO DETERMINE THE | | | SERVICE IS ADEQUITE. SEE 220.31., 215.5. | | | | | | 2} A HEAT DETECTOR MUST BE ADDED IN THE | | | KITCHEN TO COMPLY WITH 313.1.1, FBC. | | | | | | 3} THE RECEPTACLE AT THE KITCHEN ISLAND | | | MUST BE GFI PER 210.8(A)(6). | | | | | | 4} THERE IS A 50 AMP DISCONNECT SHOWN ON | | | THE KITCHEN WALL WITH NO DESIGNATION. | | | PLEASE INDICAE IT'S USE. | | | | | | 5} THE PANEL SCHEDULE MUST HAVE OCP AND | | | WIRE SIZES INDICATED FOR THE BRANCH | | | CIRCUITS AND FEEDERS TO COMPLY WITH | | | 106.3.5.4 FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|