Plan Review Notes
Plan Review Notes For Permit 05110633
Permit Number 05110633
Review Stop E
Sequence Number 5
Notes
Date Text
2006-09-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE NEW APPLIANCES IN THE
 KITCHEN ( ICE MAKER, WINE COOLER) THAT
 AREN'T LISTED IN THE LOAD CALCULATION OR
 ON THE PANEL SCHEDULE. ALSO THE
 DISHWASHER AND DISPOSAL, ALTHOUGH
 EXISTING, NUST BE INCLUDED. ALL LOADS
 MUST BE CALCULATED TO DETERMINE THE
 SERVICE IS ADEQUITE. SEE 220.31., 215.5.
  
 2} A HEAT DETECTOR MUST BE ADDED IN THE
 KITCHEN TO COMPLY WITH 313.1.1, FBC.
  
 3} THE RECEPTACLE AT THE KITCHEN ISLAND
 MUST BE GFI PER 210.8(A)(6).
  
 4} THERE IS A 50 AMP DISCONNECT SHOWN ON
 THE KITCHEN WALL WITH NO DESIGNATION.
 PLEASE INDICAE IT'S USE.
  
 5} THE PANEL SCHEDULE MUST HAVE OCP AND
 WIRE SIZES INDICATED FOR THE BRANCH
 CIRCUITS AND FEEDERS TO COMPLY WITH
 106.3.5.4 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  
  