| Plan Review Notes For Permit 05110626 |
| Permit Number |
05110626 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-31 00:00:00 | ********UNSAT ********* | | | | | | | | | 1)NOTE: PLEASE SEE OCP AND AWG FOR WATER | | | HEATER IS SHOWN TOO LARGE. MAX | | | 150%.422.11E | | | | | | 2)NOTE: PLEASE SEE NO DISCONNECT SHOWN | | | ON THE OUTSIDE OF HOUSE AS SHOWN ON | | | RISER. | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE MISSING SD IN THE | | | IMMEDIATE AREA LEADING TO FLR ABOVE PER | | | NFPA-72 11.5.1.1 (FIRST FLR) | | | | | | 4)NOTE: PLEASE SEE LOAD CALCULATIONS | | | INDICATE THE COMPRESSOR AS PART OF THE | | | LOAD CALCULATIONS, WHEN THE AHU UNIT | | | LOAD IS THE LARGER LOAD. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE NOTES FOR ELECTRICAL | | | STILL MENTIONS SD'S TO BE WIRED TO THE | | | BATH OR KITCHEN LTS, HOWEVER PLEASE SEE | | | BATH IS SHOWN AS A DEDICATED CIRCUIT | | | WHICH DOES NOT PERMIT ANY OTHER | | | ELECTRICAL ON THAT CIRCUIT. PLEASE ALSO | | | SEE NO ARC FAULT PROTECTION IS SHOWN FOT | | | KITCHEN LTS AS NOTED ON FIRST REVIEW. | | | | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|