Plan Review Notes
Plan Review Notes For Permit 05110626
Permit Number 05110626
Review Stop M
Sequence Number 1
Notes
Date Text
2005-12-12 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004), PER 2004 FBC
 13-600.
 2) NEED TO SHOW THE LOCATION OF THE
 CONDENSER UNIT ON THE PLANS.
 3) NEED TO SHOW DRAIN LINE, OR PUMP ON
 PLANS.
 4) BEDROOM #2 HAS AN 8" SUPPLY AIR DUCT
 AND NEEDS A 10" RETURN TRANSFER DUCT,
 PER 2004 FBC/R M1602.4 .
 5) CLOTHES DRYER EXHAUST NEEDS TO BE
 SHOWING ON PLANS.
 6) IS AHU IN THE CLOSET OR THE ATTIC
 PLEASE SHOW ON PLANS.
 7) NEED TO SHOW THE SIZE OF THE RETURN
 AIR GRILL IN THE 2ND. FLOOR HALLWAY.
 8) PLEASE SHOW COPPER LINE SIZES ON
 PLANS.
 IF YOU HAVE ANY QUESTIOUS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.