| Plan Review Notes For Permit 05110626 |
| Permit Number |
05110626 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-12 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON | | | FORM 600A-04 (2004), PER 2004 FBC | | | 13-600. | | | 2) NEED TO SHOW THE LOCATION OF THE | | | CONDENSER UNIT ON THE PLANS. | | | 3) NEED TO SHOW DRAIN LINE, OR PUMP ON | | | PLANS. | | | 4) BEDROOM #2 HAS AN 8" SUPPLY AIR DUCT | | | AND NEEDS A 10" RETURN TRANSFER DUCT, | | | PER 2004 FBC/R M1602.4 . | | | 5) CLOTHES DRYER EXHAUST NEEDS TO BE | | | SHOWING ON PLANS. | | | 6) IS AHU IN THE CLOSET OR THE ATTIC | | | PLEASE SHOW ON PLANS. | | | 7) NEED TO SHOW THE SIZE OF THE RETURN | | | AIR GRILL IN THE 2ND. FLOOR HALLWAY. | | | 8) PLEASE SHOW COPPER LINE SIZES ON | | | PLANS. | | | IF YOU HAVE ANY QUESTIOUS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|