| Plan Review Notes For Permit 05110617 |
| Permit Number |
05110617 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-30 07:34:18 | DENIED: | | | COMMENT 1 FROM PREVIOUS REVIEW WAS NOT ADDRESSED, | | | CERTIFICATE OF AUTHORIZATION IS NOT A VALID NUMBER. | | | PLEASE ALSO NOTE, THE SEAL IS NOT LEGIBLE ON PLAN SHEET | | | SF05 M.1.0. | | | | | | THE FOLLOWING INFORMATION IS REQUIRED FOR THE ISSUANCE | | | OF THE HOOD PERMIT. | | | PLEASE PROVIDE A DETAIL FOR THE HANGING OF THE HOOD. | | | PLEASE PROVIDE THE FOLLOWING INFORMATION: | | | A) ATTACHMENT TO THE CEILING TRUSSES | | | B) SIZE OF RODS | | | C) VIBRATION ISOLATION | | | D) MATERIAL OF EXHAUST DUCT | | | E) TYPE II HOODS SHALL COMPLY WITH 2004 FMC 507.1 AND | | | 507.4. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|