| 2006-10-25 07:44:37 | ****** UNSAT 3RD REVIEW ******* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ALONG |
| | WIHT NEW NOTE DUE TO CHNAGE IN PLAN. |
| | |
| | 1) NOTE: PLEASE SEE TWO PREVIOUS REVIEW WHICH GAVE |
| | FLORIDA ADMINISTRATIVE CODE61G15-23.002 AND FLORIDA |
| | STATUTES 471.023/481.219. PLEASE KNOW THAT THE NUMBER |
| | WHICH HAS NOW BEEN ADDED TO TITLE BLOCKS FOR REQUIRED |
| | "CERTIFICATE OF AUTHORIZATION" NUMBER OR "FIRM LICENSE" |
| | NUMBER IS NOT THAT OF WHICH IS THE REGISTRATION NUMBER |
| | AS LISTED ON TITTLE BLOCKS WHICH IS THE FLORIDA |
| | OCCUPATIONAL LICENSE NUMBER DOING BUSINESS IN THE STATE |
| | OF FLORIDA. |
| | THE NUMBER AS SHOWN IS THE OCC LICENSE WHICH CAN BE |
| | FOUND ONE WWW.SUNBIZ.ORG. PLEASE CONTACT THE FLORIDA |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION AT |
| | THEIR SITE WHICH ALSO CONTAINS INFORMATION ON HOW TO |
| | CONTACT THEM. (WWW.STATE.FL.US/DBPR) PLEASE ALSO |
| | CONTACT THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AS |
| | THEY ALSO MAY BE OF SOME ASSISTANCE AT WWW.FBPE.ORG.. |
| | PLEASE SEE AS STATED ON PREVIOUS REVIEWS IF THERE ARE |
| | ANY QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE AS PREVIOUSLY NOTED. |
| | |
| | 2) NOTE: PLEASE SEE THE EM/EXT LTS ARE SHOWN BEING |
| | SHOWN HOWEVER PLEASE SEE 700.12E WHICHREQUIRES THE |
| | BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE |
| | SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING |
| | IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | |
| | ** PLEASE KNOW WITH RESPECT TO THE EXISTING MDP, THIS |
| | WILL BE VERIFIED IN FEILD AND REDLINED ON PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |