Plan Review Notes
Plan Review Notes For Permit 05110617
Permit Number 05110617
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-10 00:00:00******** UNSAT ********
  
 ** PLEASE SEE NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
 ** PLEASE SEE NOTE BELOW EACH NOTE WHICH
 IS NOTED AS "**PREVIOUS NOTE**" IS TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 CODE REFERENCES WERE CORRECTED.
  
 **
  
 1)NOTE: NOTE #1 NO, PLEASE SEE NOTE FROM
 PREVIOUS REVIEW HAS STILL NOT BEEN
 ADDRESSED.
 PLEASE SEE THE PRINTED NAME AND LICENSE
 NUMBER OF EACH DESIGNER IS ONLY PART OF
 WHAT IS REQUIRED AND WHAT WAS NOTED ON
 PREVIOUS REVIEW. PLEASE SEE THE FLORIDA
 STATUES AS REFERENCED 481.219,471.023
 REQUIRES ANY FIRM PROVIDING
 ARCHITECTURAL OR ENGINEERING SERVICES
 SHALL OBTAIN CERTIFICATE OF
 AUTHORIZATION NUMBER(S) AND SAID NUMBERS
 FOR EACH SERVICE BEING PROVIDED. PLEASE
 SEE THAT EACH OF THESE SAID NUMBERS
 SHALL BE ON ALL TITLE BLOCKS ON PLANS
 AND ON ALL SHEETS CONTAIN TITLE BLOCKS
 FOR FIRMS AS REQUIRED BY THE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002,
 61G1-16.004
  
 ** PREVIOUS NOTE **
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND 61G1-16.004 FOR MISSING
 REQUIRED INFORMATION FOR TITLE BLOCKS
 INCLUDING LICENSING INFORMATION AS
 REUIRED UNDER FS 471.023 AND FS 481.219.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE:OK, SHEET REMOVED.
  
 3)NOTE:NOTE #3 NO, PLEASE SEE THAT A
 MCB WILL BE REQUIRED AS THE PANEL AS
 SHOWN DOES NOT MEET NEC REQUIREMENTS FOR
 THE SERVICE EQUIPMENT NOT TO CONTAIN ANY
 MORE THAN 6 SPACES OR 6 MEANS OF
 DISCONNECT. PLEASE SEE EQUIPMENT AS
 SHOWN IS CAPABLE OF CONTAINING MANY MORE
 THAN 6.
 EVEN THOUGH THIS MAY BE AN EXISTING
 CONDITION, WITH THE WORK BEING PERMITTED
 THIS WILL BE REQUIRED, NO EXCEPTIONS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE EXISTING MAIN IS
 SHOWN AS MLO, AND SHOWING MANY MORE THAN
 THE SIX SPACES (MAX) ALLOWED BY NEC,
 230.70.
 PLEASE VERIFY THAT IF A MCB IS NOT
 PRESENT,
 IF NOT A MCB WILL BE REQUIRED TO BE
 INSTALLED FOR CODE COMPLIANCE.
  
 4)NOTE: NOTE #4 NO, COULD ONLY LOCATE
 SOME OF THESE RECEPTS BEING PROTECTED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE PREVIOUS
 COMMENTS FROM FIRE REVIEW AND ELECTRICAL
 WERE TO SHOW EITHER THE NEW OR EXISTING
 LOCATIONS OF THE EM/ EXT LTS.
 PLEASE SEE A NOTE ADDED TO PLANS WHICH
 MENTIONS FOR THE "CONTRACTOR TO VERIFY".
 PLEASE SEE THIS DOES NOT SHOW THE
 CONDITIONS AS REQUESTED ON PREVIOUS
 COMMENT. PLEASE SHOW NEW OR EXIST
 LOCATIONS.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE THE NEW AND/OR
 EXISTING EMERGENCY AND EXT LT LOCATIONS
 ON ELECTRICAL PLANS TO VERIFY NFPA-101
 7.8, 7.9
 PLEASE ALSO SEE FIRE REVIEW COMMENTS.
  
  
 ** NEW NOTE **
  
 6) NOTE: PLEASE SEE COPY OF THE FLORIDA
 STATUE 553.80(2)(B) IS ATTACHED WITH
 REPSECT TO DESIGN PREOFESSIONAL AND
 REPEAT COMMENTS FOR PLAN REVIEW.
 PLEASE KNOW, THIS IS ONLY A NOTE GIVE AT
 THIS TIME.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW