| Date |
Text |
| 2006-06-10 00:00:00 | ******** UNSAT ******** |
| | |
| | ** PLEASE SEE NOTES FROM FIRST REVIEW |
| | STILL NEED TO BE ADDRESSED. |
| | ** PLEASE SEE NOTE BELOW EACH NOTE WHICH |
| | IS NOTED AS "**PREVIOUS NOTE**" IS TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | CODE REFERENCES WERE CORRECTED. |
| | |
| | ** |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE SEE NOTE FROM |
| | PREVIOUS REVIEW HAS STILL NOT BEEN |
| | ADDRESSED. |
| | PLEASE SEE THE PRINTED NAME AND LICENSE |
| | NUMBER OF EACH DESIGNER IS ONLY PART OF |
| | WHAT IS REQUIRED AND WHAT WAS NOTED ON |
| | PREVIOUS REVIEW. PLEASE SEE THE FLORIDA |
| | STATUES AS REFERENCED 481.219,471.023 |
| | REQUIRES ANY FIRM PROVIDING |
| | ARCHITECTURAL OR ENGINEERING SERVICES |
| | SHALL OBTAIN CERTIFICATE OF |
| | AUTHORIZATION NUMBER(S) AND SAID NUMBERS |
| | FOR EACH SERVICE BEING PROVIDED. PLEASE |
| | SEE THAT EACH OF THESE SAID NUMBERS |
| | SHALL BE ON ALL TITLE BLOCKS ON PLANS |
| | AND ON ALL SHEETS CONTAIN TITLE BLOCKS |
| | FOR FIRMS AS REQUIRED BY THE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002, |
| | 61G1-16.004 |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002 AND 61G1-16.004 FOR MISSING |
| | REQUIRED INFORMATION FOR TITLE BLOCKS |
| | INCLUDING LICENSING INFORMATION AS |
| | REUIRED UNDER FS 471.023 AND FS 481.219. |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE:OK, SHEET REMOVED. |
| | |
| | 3)NOTE:NOTE #3 NO, PLEASE SEE THAT A |
| | MCB WILL BE REQUIRED AS THE PANEL AS |
| | SHOWN DOES NOT MEET NEC REQUIREMENTS FOR |
| | THE SERVICE EQUIPMENT NOT TO CONTAIN ANY |
| | MORE THAN 6 SPACES OR 6 MEANS OF |
| | DISCONNECT. PLEASE SEE EQUIPMENT AS |
| | SHOWN IS CAPABLE OF CONTAINING MANY MORE |
| | THAN 6. |
| | EVEN THOUGH THIS MAY BE AN EXISTING |
| | CONDITION, WITH THE WORK BEING PERMITTED |
| | THIS WILL BE REQUIRED, NO EXCEPTIONS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE EXISTING MAIN IS |
| | SHOWN AS MLO, AND SHOWING MANY MORE THAN |
| | THE SIX SPACES (MAX) ALLOWED BY NEC, |
| | 230.70. |
| | PLEASE VERIFY THAT IF A MCB IS NOT |
| | PRESENT, |
| | IF NOT A MCB WILL BE REQUIRED TO BE |
| | INSTALLED FOR CODE COMPLIANCE. |
| | |
| | 4)NOTE: NOTE #4 NO, COULD ONLY LOCATE |
| | SOME OF THESE RECEPTS BEING PROTECTED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE PREVIOUS |
| | COMMENTS FROM FIRE REVIEW AND ELECTRICAL |
| | WERE TO SHOW EITHER THE NEW OR EXISTING |
| | LOCATIONS OF THE EM/ EXT LTS. |
| | PLEASE SEE A NOTE ADDED TO PLANS WHICH |
| | MENTIONS FOR THE "CONTRACTOR TO VERIFY". |
| | PLEASE SEE THIS DOES NOT SHOW THE |
| | CONDITIONS AS REQUESTED ON PREVIOUS |
| | COMMENT. PLEASE SHOW NEW OR EXIST |
| | LOCATIONS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE THE NEW AND/OR |
| | EXISTING EMERGENCY AND EXT LT LOCATIONS |
| | ON ELECTRICAL PLANS TO VERIFY NFPA-101 |
| | 7.8, 7.9 |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS. |
| | |
| | |
| | ** NEW NOTE ** |
| | |
| | 6) NOTE: PLEASE SEE COPY OF THE FLORIDA |
| | STATUE 553.80(2)(B) IS ATTACHED WITH |
| | REPSECT TO DESIGN PREOFESSIONAL AND |
| | REPEAT COMMENTS FOR PLAN REVIEW. |
| | PLEASE KNOW, THIS IS ONLY A NOTE GIVE AT |
| | THIS TIME. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |