| Plan Review Notes For Permit 05110617 |
| Permit Number |
05110617 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-14 00:00:00 | -------------------DENIED--------------- | | | | | | 1) IF HOOD FAN IS WITHIN 10' OF ROOF | | | EDGE A GUARD IS REQUIRED PER FBC,M | | | 304.10 | | | | | | 2)PAGE E.1.0 KEYED NOTE #8 CALLS FOR | | | CONDENSERS TO BE MOUNTED ON ROOF.ARE | | | THESE NEW OR BEING RELOCATED?PROVIDE | | | DETAIL FOR ROOFTOP INSTALLATION OF | | | EQUIPMENT WITH ENGINEERING FOR STANDS TO | | | SHOW COMPLIANCE WITH WIND LOAD AND ROOF | | | CLEARANCE REQUIREMENTS OF FBC 1509.7 | | | | | | 3) EQUIPMWNT ON ROOF REQUIRING SERVICE | | | NEEDS PERMENANT ACCESS PER FBC,M 306.5 | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | RON REGUEIRO @ 561.805.6734 OR PATTY | | | KRAUSS @ 561.805.6719 |
|