2005-12-14 00:00:00-------------------DENIED---------------
  
 1) IF HOOD FAN IS WITHIN 10' OF ROOF
 EDGE A GUARD IS REQUIRED PER FBC,M
 304.10
  
 2)PAGE E.1.0 KEYED NOTE #8 CALLS FOR
 CONDENSERS TO BE MOUNTED ON ROOF.ARE
 THESE NEW OR BEING RELOCATED?PROVIDE
 DETAIL FOR ROOFTOP INSTALLATION OF
 EQUIPMENT WITH ENGINEERING FOR STANDS TO
 SHOW COMPLIANCE WITH WIND LOAD AND ROOF
 CLEARANCE REQUIREMENTS OF FBC 1509.7
  
 3) EQUIPMWNT ON ROOF REQUIRING SERVICE
 NEEDS PERMENANT ACCESS PER FBC,M 306.5
  