| 2005-12-24 00:00:00 | ************** UNSAT ************* |
| | |
| | |
| | **************************************** |
| | PLEASE SEE THE WRONG CODES REFERENCED ON |
| | THE COVER SHEETS AND DESIGNS. |
| | PLEASE SEE WE ARE CURRENTLY UNDER THE |
| | 2004 FBC. PLEASE SEE ANY CHANGES DUE TO |
| | NEW REQUIREMENTS FOR EXSITING BUILDINGS. |
| | PLEASE ADJUST AS NEEDED. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS. |
| | THE NEC IN EFFECT IS THE 2002. |
| | |
| | 1)NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND |
| | 61G1-16.004 FOR MISSING REQUIRED |
| | INFORMATION FOR TITLE BLOCKS INCLUDING |
| | LICENSING INFORMATION AS REUIRED UNDER |
| | FS 471.023 AND FS 481.219. |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE ZONING COMMENTS WITH |
| | RESPECT TO THE LAST SHEET IN EACH SET. |
| | PLEASE SEE THAT ALL SIGNAGE WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMITS. |
| | PLEASE REMOVE THIS SHEETS FROM SETS. |
| | ** PLEASE KNOW, THIS SHEETS IS ALSO A |
| | SEALED PHOTOCPOY OF THE ENGINEER'S |
| | ORIGINAL SIGNATURE. PLEASE BE SURE |
| | SUBMIT THE CORRECTED SHEETS AS FS |
| | 471.025 FAC 61G15-23.002 REQUIRES THE |
| | ORIGINAL "WET" SIGNATURE AND DATE. |
| | |
| | 3)NOTE: PLEASE SEE EXISTING MAIN IS |
| | SHOWN AS MLO, AND SHOWING MANY MORE THAN |
| | THE SIX SPACES (MAX) ALOOWED BY NEC, |
| | 230.70. |
| | PLEASE VERIFY THAT A MCB IS NOT PRESENT, |
| | IF NOT A MCB WILL BE REQUIRED TO BE |
| | INSTALLED FOR CODE COMPLIANCE. |
| | |
| | 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | 5)NOTE: PLEASE PROVIDE THE NEW AND/OR |
| | EXISTING EMERGENCY AND EXT LT LOCATIONS |
| | ON ELECTRICAL PLANS TO VERIFY NFPA-101 |
| | 7.8, 7.9 |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |