Plan Review Notes
Plan Review Notes For Permit 05110617
Permit Number 05110617
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-01 00:00:00 
  
 DENIED
  
 1) A TITLE BLOCK WITH THE INFORMATION
 SPECIFIED PER 61G1-16.004 FAC SHALL BE
 PRESENT ON DRAWINGS ISSUED BY THE
 RESPONSIBLE ARCHITECT AND MUST, AT A
 MINIMUM CONTAIN
 1)FIRM NAME,ADDRESS, AND TELEPHONE #
 2)FIRM LICENCE #
 3)NAME OF PROJECT
 4)DATE PREPARED
 5)A SPACE FOR SIGNATURE & DATED SEAL
 6)A SPACE FOR PRINTED NAME OF PERSON
 SEALING THE DOCUMENT
  
 2) MAKE CHANGES TO PAGE G.0.1 TO REFLECT
 FBC 2004 AND BUILDING DISCRIPTION
  
 3) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (1)- (5). PLEASE SEE THAT
 THE CA # YOU HOLD IN THE STATE OF
 FLORIDA IS UNDER WOLFGANG DOERSCHLAG
 ARCHITECTS LTD., INC AND NOT WD PARTNERS
  
 4) EQUIPMENT THAT IS TO BE PLACED ON
 ROOF, INDICATE IF IT IS REPLACEMENT OR
 NEW AND IF NEW CONFIRM THAT ROOF IS
 DESIGNED FOR ADDED LOADS. ALSO WILL
 INSTALLATION OF EQUIPMENT REQUIRE ROOF
 MEMBRANE WORK AND A ROOF PERMIT.
 EQUIPMENT STANDS WILL REQUIRE PRODUCT
 APPROVALS PER 9B-72 FAC
  
 5) 8X10 STORAGE SHED ON SHEET 1 WILL
 REQUIRE A SEPARATE PERMIT WITH 2 COPIES
 OF SURVEY SHOWING SETBACKS TO SHED. IF
 SHED IS BUILT BY A STATE OF FLORIDA
 APPROVED MODULAR BUILDING MANUFACTURER
 ALSO SUBMIT THE PRODUCT APPROVALS, IF
 BUILT ON SITE DRAWINGS WILL BE REQUIRED
 THAT WILL MEET THE WIND LOADS OF 1609
 FBC 2004. WEST PALM BEACH IS 140 MPH 3
 SECOND GUST, EXP. B, IMPORTACE FACTOR 1
  
 6) FOOD AND BEVERAGE COUNTERS SHALL MEET
 THE REQUIREMENTS OF 11-5.2 OF THE
 FLORIDA ACCESSABILITY CODE FBC 2004
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  