| Plan Review Notes For Permit 05110599 |
| Permit Number |
05110599 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-26 00:00:00 | DENIED 2ND TIME | | | REFERENCE: FBC-2004 SWIMMING POOLS | | | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING | | | INFORMATION REQUIRED FOR PLAN REVIEW. | | | 1. THERE IS NO POOL HEATER INDICATED ON | | | POOL SPECIFICATIONS, WITH MODEL NUMBER, | | | OR IN THE EQUIPMENT LAYOUT OR LEGEND. | | | PRINT MUST SHOW THIS. ALSO SEE PAGE 14 | | | FIGURE 27 IN THE POOL HEATER SUBMITTAL. | | | THIS MODEL HEATER HAS NO POSITIVE MEANS | | | OF RETAINING WATER IN HEATER WHEN PUMP | | | IS NOT IN OPERATION, THEREFORE AN | | | EXTERNAL HARTFORD LOOP IS REQUIRED FOR | | | THE HEATER. PLEASE INDICATE THIS ON THE | | | EQUIPMENT LAYOUT DRAWING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 |
|