Plan Review Notes
Plan Review Notes For Permit 05110599
Permit Number 05110599
Review Stop P
Sequence Number 2
Notes
Date Text
2006-01-26 00:00:00DENIED 2ND TIME
 REFERENCE: FBC-2004 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW.
 1. THERE IS NO POOL HEATER INDICATED ON
 POOL SPECIFICATIONS, WITH MODEL NUMBER,
 OR IN THE EQUIPMENT LAYOUT OR LEGEND.
 PRINT MUST SHOW THIS. ALSO SEE PAGE 14
 FIGURE 27 IN THE POOL HEATER SUBMITTAL.
 THIS MODEL HEATER HAS NO POSITIVE MEANS
 OF RETAINING WATER IN HEATER WHEN PUMP
 IS NOT IN OPERATION, THEREFORE AN
 EXTERNAL HARTFORD LOOP IS REQUIRED FOR
 THE HEATER. PLEASE INDICATE THIS ON THE
 EQUIPMENT LAYOUT DRAWING.
  
 END OF COMMENTS:
  