2006-03-13 00:00:00------------------DENIED----------------
 1) PER COMMENT #2 FROM PREVIOUS REVIEW,
 ONLY ONE OF THE TWO EXISTING DUCTS
 TRAVELING FROM SUITE 520 INTO SUITE 510
 THROUGH AN NEW 1-HOUR RATED WALL SHOWS A
 FIRE DAMPER. I HAVE HIGHLIGHTED THIS
 LOCATION.
  
 2) PLAN INDICATES NEW TENANT SEPARATION
 WALL BETWEEN SUITES 510 AND 560. PLAN
 ALSO SHOWS A NEW TENANT SEPARATION WALL
 BETWEEN SUITES 540 AND 550. ALSO BETWEEN
 SUITES 510 AND 520. PROJECT DATA BLOCK
 ON SHEET T INDICATE TENANT SEPARATION
 WALLS TO BE 1-HOUR RATED. PLEASE
 INDICATE CORRECT WALL ASSEMBLY TYPE ON
 PAGE A1.1 AND TREAT ALL WALL
 PENETRATIONS AS RATED PENETRATIONS BY
 INDICATING NEW FIRE DAMPER LOCATIONS.
  