| Plan Review Notes For Permit 05110591 |
| Permit Number |
05110591 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-13 00:00:00 | ------------------DENIED---------------- | | | 1) PER COMMENT #2 FROM PREVIOUS REVIEW, | | | ONLY ONE OF THE TWO EXISTING DUCTS | | | TRAVELING FROM SUITE 520 INTO SUITE 510 | | | THROUGH AN NEW 1-HOUR RATED WALL SHOWS A | | | FIRE DAMPER. I HAVE HIGHLIGHTED THIS | | | LOCATION. | | | | | | 2) PLAN INDICATES NEW TENANT SEPARATION | | | WALL BETWEEN SUITES 510 AND 560. PLAN | | | ALSO SHOWS A NEW TENANT SEPARATION WALL | | | BETWEEN SUITES 540 AND 550. ALSO BETWEEN | | | SUITES 510 AND 520. PROJECT DATA BLOCK | | | ON SHEET T INDICATE TENANT SEPARATION | | | WALLS TO BE 1-HOUR RATED. PLEASE | | | INDICATE CORRECT WALL ASSEMBLY TYPE ON | | | PAGE A1.1 AND TREAT ALL WALL | | | PENETRATIONS AS RATED PENETRATIONS BY | | | INDICATING NEW FIRE DAMPER LOCATIONS. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|