Plan Review Notes
Plan Review Notes For Permit 05110591
Permit Number 05110591
Review Stop P
Sequence Number 1
Notes
Date Text
2006-01-27 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC 2004 BUILDING CH 11
 1) SHT A1.1 TOILET RM 545
 SEC 11-4.22.2 DOORS.
 ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 2) SHT A4.1 DETAIL L1,H1 CABINET ELV.
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
 3) SHT P-1
 SECTION P909WET VENTING
  
 ?P909.1 WET VENT PERMITTED. ANY
 COMBINATION OF FIXTURES WITHIN TWO
 BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL ARE PERMITTED TO BE VENTED
 BY A WET VENT.THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES
 AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF
 THE FLOW IN THE DRAIN PIPE TO THE MOST
 DOWNSTREAM FIXTURE DRAIN CONNECTION
 TO THE HORIZONTAL BRANCH DRAIN.ONLY
 THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN.ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
 END OF COMMENTS, QUESTIONS 561-805-6692
  