2005-12-13 00:00:00------------------DENIED----------------
  
 1) PAGE M1 DRAWING NOTE #3 SHOWS FIVE
 NEW 48X12 T.A.OS LOCATED AT TENANT
 SEPERATION 1-HOUR RATED WALLS. PLAN DOES
 NOT SHOW FIRE DAMPERS AT FOUR OF THEM.
 FIRE DAMPERS ARE REQUIRED AT THESE
 LOCATIONS PER FBC,M 607.5.
  
 2) PAGE M1 SHOWS NEW TENANT SEPERATION
 1-HOUR RATED WALL BETWEEN SUITES 510 AND
 520 WITH TWO EXISTING DUCTS RUNNING
 THROUGH IT. FIRE DAMPERS ARE REQUIRED AT
 THESE LOCATIONS PER FBC,M 607.5.
  