| Plan Review Notes For Permit 05110591 |
| Permit Number |
05110591 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-13 00:00:00 | ------------------DENIED---------------- | | | | | | 1) PAGE M1 DRAWING NOTE #3 SHOWS FIVE | | | NEW 48X12 T.A.OS LOCATED AT TENANT | | | SEPERATION 1-HOUR RATED WALLS. PLAN DOES | | | NOT SHOW FIRE DAMPERS AT FOUR OF THEM. | | | FIRE DAMPERS ARE REQUIRED AT THESE | | | LOCATIONS PER FBC,M 607.5. | | | | | | 2) PAGE M1 SHOWS NEW TENANT SEPERATION | | | 1-HOUR RATED WALL BETWEEN SUITES 510 AND | | | 520 WITH TWO EXISTING DUCTS RUNNING | | | THROUGH IT. FIRE DAMPERS ARE REQUIRED AT | | | THESE LOCATIONS PER FBC,M 607.5. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | RON REGUEIRO @ 561.805.6734 |
|