Plan Review Notes
Plan Review Notes For Permit 05110586
Permit Number 05110586
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-08 00:00:00DENIED;
 1.SCUPPERS, PAGE 5 PLEASE SIZE PER
 FBC-2004 PLUMBING TABLE 1106.7.
 2.SECONDARY DRAINS REQUIRED PER 1107.3.
 SHOW CALKS ON PLANS.
 3.SIZE DOWN SPOUTS PER TABLE 1106.2.
 4.PAGE 7, HORIZONTAL DRY VENTS ARE NOT
 TO CODE SEC.905.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695