Plan Review Notes
Plan Review Notes For Permit 05110586
Permit Number 05110586
Review Stop M
Sequence Number 1
Notes
Date Text
2005-12-07 00:00:00*** DENIED ***
 1) RETURN AIR REQUIRED IN MASTER
 BEDROOM, PER 2004 FBC/R M1602.4 .
 2) SUPPLY AIR DUCT FROM AHU TO TRIANGLE
 NOT SIZED.
 3) LOCATION OF CONDENSER UNIT NOT
 SHOWING ON MECH. PLANS .
 4) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004), PER 2004 FBC
 13-600.0 ABC .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.