| 2005-12-07 00:00:00 | *********** UNSAT ************* |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE: PLEASE SEE MANY MISSING RECEPTS |
| | PER 210.52 |
| | |
| | 3)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52H |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.63 FOIR AHU LOCATED IN ATTIC. |
| | |
| | 5)NOTE: PLEASE MISSING RECEPT REQUIRED |
| | FOR BATH/POWDER RM PER 210.52D. |
| | |
| | 6)NOTE: PLEASE INDICATE ALL REQUIRED |
| | RECEPTS TO BE GFI AS GFI. |
| | PLEASE SEE BATH RMS, GARAGE ETC. |
| | 210.8A1,2 ETC. |
| | |
| | 7)NOTE: PLEASE SEE PLANS SHOW SD IN |
| | BATHROOM AND OUTSIDE BATHRM DOOR WITHIN |
| | 3'. PLEASE SEE THIS IS NOT PERMITTED. |
| | NFPA-72 11.8.3.5 |
| | PLEASE ALSO SEE ONE BEDRM WHERE SD LOOKS |
| | TO BE JUST OUTSIDE THE DOOR, WHERE |
| | REQUIRED TO BE LOCATED INSIDE. THESE ARE |
| | REDLINED ON PLANS FOR CLARIFICATION. |
| | |
| | 8)NOTE: PLEASE SEE MISSING DEDICATED GDO |
| | CIRCUIT IN PANELAND IN LOAD CALCS. |
| | 215.5,230.24, 220 ETC . |
| | |
| | 9)NOTE: PLEASESEE THAT PLANS SPECIFY |
| | THE CODE WHICH IS IN EFFECT.(2002) |
| | PLEASE ALSO SEE PLANS CALL FOR ALL TO |
| | MEET CITY OF RIVERA BEACH? PLEASE SEE |
| | THIS PROJECT IS LCATED IN THE CITY OF |
| | WEST PALM BEACH. |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU 10KW HEAT. |
| | 50A IS NOT LARGE ENOUGH. |
| | |
| | 11)NOTE: PLEASE SEE 210.52D,210.11C3, |
| | WHICH REQUIRES ALL BATH CIRCUITS (S) TO |
| | BE 20A AND #12 AWG. PLEASE SEE 20A OCP |
| | SHOWN ON #14 AWG ETC. |
| | |
| | 12)NOTE: PLEASE SEE SEE PLANS INDICATE A |
| | "AHU" PAD LOCATED OUTSIDE? |
| | PLEASE ASJUST AS NEEDED FOR CU. |
| | PLEASE ALSO SEE MISSING DISCONNECT PER |
| | 440.11 NOT SHOWN. |
| | |
| | 13)NOTE: PLEASE SEE NOTES ON PLANS |
| | INDICATE THE SD'S WIRED TO BATH AND |
| | KITCHEN LIGHTING CIRCUIT. PLEASE SEE |
| | SD'S ARE ALL REQUIRED TO BE WIRED |
| | "IN-LINE" (NFPA 72_) AND ARE ALL |
| | REQUIRED TO BE AFCI PROTECTED AS PER |
| | 210.12 OF THE 2002 NEC. |
| | PLEASE ADJUST NOTE, UNLESS AFCI BRKRS |
| | ARE GOING TO BE NOTED FOR KITCHEN LTS |
| | AND BATH LTS. |
| | PLEASE CALL TO GO OVER THIS SCENERIO. |
| | |
| | 14)NOTE: PLEASE SEE 210.11C2 WHICH |
| | REQUIRES LAUNDRY/WASHER CIRCUITS TO HAVE |
| | A MIN OF 1.5KW FOR EACH. PLEASE SEE |
| | PLANS INDICATE LESS VA. |
| | 215.5 |
| | |
| | 15)NOTE: PLEASE SEE 210.52C2,4 FOR |
| | KITCHEN ISLAND AND REQUIRES GFI RECEPTS |
| | FOR SEPARATE SPACES. |
| | PLEASE SEE A GFI IS BEING SHOWN AS |
| | SWICTHED?IS THIS FOR DISPOSAL?TYPICALLY |
| | THIS IS NOT GFI. PLEASE ALSO SEE DW IS |
| | ALSO SHOWN AAS GFI, YET ISLAND RECEPT |
| | WHICH IS REQUIRED TO BE GFI IS NOT |
| | INDCATED AS SO. |
| | 210.8A6 |
| | |
| | 16)NOTE: PLEASE SEE THE NOC RECORDED ON |
| | 9/2/05 HAS EXPIRED AND WILL BE REQUIRED |
| | TO BE RE-RECORDED. |
| | PLEASE SEE FS 713.12(2) WHICH MENTIONS, |
| | IF WORK HAS NOT COMMENCED WITH IN 90 |
| | DAYS OF RECORDING, SUCH NOC SHALL BECOME |
| | VOID. |
| | |
| | 17)NOTE: PLEASE SEE LOADS FOR SM APPL, |
| | TO BE A MIN OF 1500VA. |
| | 210.11C3 |
| | |
| | 18)NOTE: PLEASE SEE MANY OTHER LOADS |
| | INDICATED ON PANEL SCHEDULE DO NOT SEEM |
| | TO CORRELATE. |
| | PLEASE ALSO SEE LIGHTING LOADS ON 15A |
| | CIRCUITS, SHOWN EXCEED RATING OF |
| | CIRCUITS.1440 VA 15A. 1920VA 20A. |
| | 215.5 |
| | |
| | |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW AND IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | **PLEASE SEE MANY OF THE ABOVE ITEMS |
| | HAVE BEEN REDLNED ON PLANS WHICH ARE |
| | NOTED. |
| | |