2005-12-07 00:00:00*** DENIED ***
 1) GENERATOR LOCATION NOT SHOWING ON
 SIGHT PLAN.
 2) PLEASE NOTE GENERATOR EXHUST MUST BE
 TEN FEET AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENINGS.
 3) NEED TO FILE A NOTICE OF
 COMMENCEMENT.