2005-12-07 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PLAN SHOWS A 15KW GENERATOR, THE
 APPLICATION INDICATES A 13 KW GENERATOR,
 PLEASE CORRELATE.
  
 2} THE LOAD IN THE PANEL TO BE SERVED BY
 THE GENERATOR IS 22.56KW. THE GENERATOR
 MUST BE SIZED PER 702.5.
  
 3} INDICATE THE PHYSICAL LOCATION OF THE
 TRANSFER SWITCH ON THE PLAN, AND THE GEN
 FEEDER DISCONNECTING MEANS AT THE
 ENTRANCE OF THE BUILDING PER 225.31
 THROUGH 225.37.
  