| Notes |
| Date |
Text |
| 2005-12-07 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PLAN SHOWS A 15KW GENERATOR, THE | | | APPLICATION INDICATES A 13 KW GENERATOR, | | | PLEASE CORRELATE. | | | | | | 2} THE LOAD IN THE PANEL TO BE SERVED BY | | | THE GENERATOR IS 22.56KW. THE GENERATOR | | | MUST BE SIZED PER 702.5. | | | | | | 3} INDICATE THE PHYSICAL LOCATION OF THE | | | TRANSFER SWITCH ON THE PLAN, AND THE GEN | | | FEEDER DISCONNECTING MEANS AT THE | | | ENTRANCE OF THE BUILDING PER 225.31 | | | THROUGH 225.37. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|