| Plan Review Notes For Permit 05110569 |
| Permit Number |
05110569 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-13 00:00:00 | *** PROVISO *** | | | 1) GENERATOR EXHUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS | | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | | TEN FEET AWAY FROM ADJECENT BUILDING | | | OPENS. | | | 2) DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS MUST BE ON JOB SITE. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|