| 2006-08-22 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} ALL DOCUMENTS SUBMITTED OR |
| | RESUBMITTED FOR REVIEW, THAT ARE |
| | NECESSARY TO COMPLETE THE ORIGINAL |
| | DESIGN, MUST BE SUBMITTED BY THE |
| | DESIGNER OF RECORD. IN THIS CASE THE |
| | ARCHITECT, NOT THE OWNER/BUILDER OR AN |
| | ELECTRICAL CONTRACTOR. 481.221 F.S. |
| | |
| | NOTE: THE ELECTRICAL CONTRACTOR DRAWING |
| | PLANS UNDER THE ENGINEERING EXEMPTION |
| | 471.003, MUST FIRST OF ALL BE THE |
| | CONTRACTOR OF RECORD, HAVING OBTAINED A |
| | PERMIT BY APPLICATIION OR BEING SIGNED |
| | ON THE ORIGINAL APPLICATION, AND |
| | ASSIGNED A PERMIT NUMBER. AND SECOND, |
| | MUST HAVE DRAWN THE PLANS ORIGINALLY. |
| | |
| | 2} THE PREVIOUS COMMENTS STILL NEED TO |
| | BE ADDRESSED BY THE ARCHITECT ON NEW |
| | SHEETS, NOT HAND DRAWN, AND CONTAIN THE |
| | DATE OF THE CHANGE AS REQUIRED BY |
| | 481.221. |
| | |
| | REGARDING COTTAGE #1. |
| | |
| | A) THE GROUNDING ELECTRODE CONDUCTOR |
| | MUST BE #2 CU TO COMPLY WITH 250.66, FOR |
| | A 250 AMP SERVICE, WHICH REQUIRES #4/0 |
| | FEED CONDUCTORS. |
| | |
| | B) THE #8 GROUND RAN WITH THE FEEDERS |
| | FROM THE 125 AMP MAIN BREAKER TO THE 2ND |
| | FLOOR PANEL IS REQUIRED TO BE #6 PER |
| | 250.122. #8 IS LISTED FOR A 100 AMP |
| | BREAKER. |
| | |
| | C) THERE ARE TWOKITCHENS UNITS ON THE |
| | SECOND FLOOR, NOT ALLOWED BY ZONING. |
| | |
| | D} INDICATE HOW THE PANEL ON THE 2ND |
| | FLOOR IS BEING FED, SEE 230.3. |
| | |
| | E} PANEL SCHEDULES AND CALCULATIONS MUST |
| | BE SUBMITTED BY THE DESIGNER OF RECORD. |
| | |
| | |
| | COTTAGE #2. |
| | |
| | INDICATE THE PANEL LOCATION, DISCONNECTS |
| | PER 225.31, AND GROUNDING PER 250.32 |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |