2006-08-22 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} ALL DOCUMENTS SUBMITTED OR
 RESUBMITTED FOR REVIEW, THAT ARE
 NECESSARY TO COMPLETE THE ORIGINAL
 DESIGN, MUST BE SUBMITTED BY THE
 DESIGNER OF RECORD. IN THIS CASE THE
 ARCHITECT, NOT THE OWNER/BUILDER OR AN
 ELECTRICAL CONTRACTOR. 481.221 F.S.
  
 NOTE: THE ELECTRICAL CONTRACTOR DRAWING
 PLANS UNDER THE ENGINEERING EXEMPTION
 471.003, MUST FIRST OF ALL BE THE
 CONTRACTOR OF RECORD, HAVING OBTAINED A
 PERMIT BY APPLICATIION OR BEING SIGNED
 ON THE ORIGINAL APPLICATION, AND
 ASSIGNED A PERMIT NUMBER. AND SECOND,
 MUST HAVE DRAWN THE PLANS ORIGINALLY.
  
 2} THE PREVIOUS COMMENTS STILL NEED TO
 BE ADDRESSED BY THE ARCHITECT ON NEW
 SHEETS, NOT HAND DRAWN, AND CONTAIN THE
 DATE OF THE CHANGE AS REQUIRED BY
 481.221.
  
 REGARDING COTTAGE #1.
  
 A) THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE #2 CU TO COMPLY WITH 250.66, FOR
 A 250 AMP SERVICE, WHICH REQUIRES #4/0
 FEED CONDUCTORS.
  
 B) THE #8 GROUND RAN WITH THE FEEDERS
 FROM THE 125 AMP MAIN BREAKER TO THE 2ND
 FLOOR PANEL IS REQUIRED TO BE #6 PER
 250.122. #8 IS LISTED FOR A 100 AMP
 BREAKER.
  
 C) THERE ARE TWOKITCHENS UNITS ON THE
 SECOND FLOOR, NOT ALLOWED BY ZONING.
  
 D} INDICATE HOW THE PANEL ON THE 2ND
 FLOOR IS BEING FED, SEE 230.3.
  
 E} PANEL SCHEDULES AND CALCULATIONS MUST
 BE SUBMITTED BY THE DESIGNER OF RECORD.
  
  
 COTTAGE #2.
  
 INDICATE THE PANEL LOCATION, DISCONNECTS
 PER 225.31, AND GROUNDING PER 250.32
  