Plan Review Notes
Plan Review Notes For Permit 05110560
Permit Number 05110560
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-23 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM AND
 LOAD CALCULATIONS FOR THE SERVICE. SHOW
 ALL FEEDERS. 215.5.
  
 2} SHOW COMPLIANCE WITH ARTICLE 225.31
 AND 250.32 FOR THE SEPERATE STRUCTURES.
  
 3} PROVIDE PANEL SCHEDULES FOR THE
 COTTAGE PANELS SO BRANCH CIRCUIT CODE
 COMPLIANCE CAN BE DETERMINED. 210.52.
  
 4} IN REFERENCE TO THE ELECTRICAL PANEL
 IN THE STORAGE ROOM, SEE 240.24(D) NOT
 IN VICINITY OF EASILY IGNITIBLE
 MATERIAL. OVERCURRENT DEVICES SHALL NOT
 BE LOCATED IN THE VICINITY OF EASILY
 IGNITIBLE MATERIAL, SUCH AS IN CLOTHES
 CLOSETS. EXAMPLES OF LOCATIONS WHERE
 COMBUSTIBLE MATERIALS MAY BE STORED ARE
 LINEN CLOSETS, PAPER STORAGE CLOSETS,
 AND CLOTHES CLOSETS.
  
 THE FIRST THREE COMMENTS WERE ON THE
 PREVIOUS REVIEW. PLEASE SEE FLORIDA
 STATUTE 553.80(2)(B), ATTACHED. THIS IS
 THE SECOND REVIEW WITH AN INCOMPLETE, OR
 NO, PLAN OF THE SERVICE, CAUSING THE
 PLANS TO BE REJECTED AND ULTIMETLY
 RESUBMITTED A THIRD TIME, CREATING AN
 UNNECESSARY DELAY IN PERMITTING AND
 CONSRUCTION. PLEASE SEE THE STATUTE IS
 DIRECTED TO THE DESIGNER OF RECORD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]