| 2006-05-23 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE PROVIDE A RISER DIAGRAM AND |
| | LOAD CALCULATIONS FOR THE SERVICE. SHOW |
| | ALL FEEDERS. 215.5. |
| | |
| | 2} SHOW COMPLIANCE WITH ARTICLE 225.31 |
| | AND 250.32 FOR THE SEPERATE STRUCTURES. |
| | |
| | 3} PROVIDE PANEL SCHEDULES FOR THE |
| | COTTAGE PANELS SO BRANCH CIRCUIT CODE |
| | COMPLIANCE CAN BE DETERMINED. 210.52. |
| | |
| | 4} IN REFERENCE TO THE ELECTRICAL PANEL |
| | IN THE STORAGE ROOM, SEE 240.24(D) NOT |
| | IN VICINITY OF EASILY IGNITIBLE |
| | MATERIAL. OVERCURRENT DEVICES SHALL NOT |
| | BE LOCATED IN THE VICINITY OF EASILY |
| | IGNITIBLE MATERIAL, SUCH AS IN CLOTHES |
| | CLOSETS. EXAMPLES OF LOCATIONS WHERE |
| | COMBUSTIBLE MATERIALS MAY BE STORED ARE |
| | LINEN CLOSETS, PAPER STORAGE CLOSETS, |
| | AND CLOTHES CLOSETS. |
| | |
| | THE FIRST THREE COMMENTS WERE ON THE |
| | PREVIOUS REVIEW. PLEASE SEE FLORIDA |
| | STATUTE 553.80(2)(B), ATTACHED. THIS IS |
| | THE SECOND REVIEW WITH AN INCOMPLETE, OR |
| | NO, PLAN OF THE SERVICE, CAUSING THE |
| | PLANS TO BE REJECTED AND ULTIMETLY |
| | RESUBMITTED A THIRD TIME, CREATING AN |
| | UNNECESSARY DELAY IN PERMITTING AND |
| | CONSRUCTION. PLEASE SEE THE STATUTE IS |
| | DIRECTED TO THE DESIGNER OF RECORD. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |