| Plan Review Notes For Permit 05110560 |
| Permit Number |
05110560 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-15 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A RISER DIAGRAM AND | | | LOAD CALCULATIONS FOR THE SERVICE. SHOW | | | ALL FEEDERS. 215.5. | | | | | | 2} SHOW COMPLIANCE WITH ARTICLE 225.31 | | | AND 250.32 FOR THE SEPERATE STRUCTURES. | | | | | | 3} PROVIDE PANEL SCHEDULES FOR THE | | | COTTAGE PANELS SO BRANCH CIRCUIT CODE | | | COMPLIANCE CAN BE DETERMINED. 210.52. | | | | | | 4} SEE R313 FBC RESIDENTIALCODE FOR | | | SMOKE DETECTOR REQUIREMENTS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|