Plan Review Notes
Plan Review Notes For Permit 05110560
Permit Number 05110560
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-15 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM AND
 LOAD CALCULATIONS FOR THE SERVICE. SHOW
 ALL FEEDERS. 215.5.
  
 2} SHOW COMPLIANCE WITH ARTICLE 225.31
 AND 250.32 FOR THE SEPERATE STRUCTURES.
  
 3} PROVIDE PANEL SCHEDULES FOR THE
 COTTAGE PANELS SO BRANCH CIRCUIT CODE
 COMPLIANCE CAN BE DETERMINED. 210.52.
  
 4} SEE R313 FBC RESIDENTIALCODE FOR
 SMOKE DETECTOR REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026