| 2006-02-16 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) DETAIL 2 ON SHEET 2 OF 4 SHOWS WOOD |
| | TO WOOD CONNECTION, IS THIS NOT WOOD TO |
| | STEEL COLUMN, ALSO ARE EXISTING WALLS |
| | WOOD AS IN LEGEND OR BLOCK, CLARIFY |
| | |
| | 2) DETAILS 1/3 AND 6/3 2X6 WALLS REQUIRE |
| | R19 INSULATION |
| | |
| | 3) DESIGN PRESSURE TABLE 1606.2E HAS |
| | CHANGED IN 2004 FBC TO TABLE 1609.6B |
| | |
| | 4) DETAILS ON FRAME-IN DIFFER FROM |
| | DETAIL 6/3. PC64 CONNECTOR IS ATTACHED |
| | TO 3X8 HEADER WHICH IS TIGHT TO EXISTING |
| | BEAM, CLARIFY |
| | |
| | 5) SPECIFY ANCHORS TO BE USED IN ABU46 |
| | AND 6X6 COLUMNS (EG. WEDGE ANCHORS, |
| | EPOXYED THREADED ROD OR RBF #5X? ETC.) |
| | |
| | 6) CHECK SIMPSON CONNECTOR PC46 AS |
| | EXISTING BEAM OVER 2X6 WALL SHOULD BE |
| | 5 1/2" WIDE AND MAY NEED PC64 |
| | |
| | 7) ENERGY CALC'S SHALL BE SIGNED AND |
| | DATED BY OWNER AGENT |
| | |
| | 8) SIMPSON WOOD CONNECTORS REQUIRE |
| | PRODUCT APPROVALS. FL STATE COVER SHEET |
| | WITH ALL CONNECTORS THAT WILL BE USED |
| | MARKED ON IT WILL BE OK (NO NOA'S WILL |
| | BE REQUIRED) |
| | |
| | 9) THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 WPB |
| | AMENDMENTS TO FBC 2004. (APPROVED BY |
| | ENGINEER ON DRAWINGS) STAMP APPROVED AND |
| | INITIAL |
| | |
| | NOTE: IF NEEDED CALL FOR CLARIFICATION |
| | |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |