Plan Review Notes
Plan Review Notes For Permit 05110557
Permit Number 05110557
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-16 00:00:00 
  
 DENIED
  
 1) DETAIL 2 ON SHEET 2 OF 4 SHOWS WOOD
 TO WOOD CONNECTION, IS THIS NOT WOOD TO
 STEEL COLUMN, ALSO ARE EXISTING WALLS
 WOOD AS IN LEGEND OR BLOCK, CLARIFY
  
 2) DETAILS 1/3 AND 6/3 2X6 WALLS REQUIRE
 R19 INSULATION
  
 3) DESIGN PRESSURE TABLE 1606.2E HAS
 CHANGED IN 2004 FBC TO TABLE 1609.6B
  
 4) DETAILS ON FRAME-IN DIFFER FROM
 DETAIL 6/3. PC64 CONNECTOR IS ATTACHED
 TO 3X8 HEADER WHICH IS TIGHT TO EXISTING
 BEAM, CLARIFY
  
 5) SPECIFY ANCHORS TO BE USED IN ABU46
 AND 6X6 COLUMNS (EG. WEDGE ANCHORS,
 EPOXYED THREADED ROD OR RBF #5X? ETC.)
  
 6) CHECK SIMPSON CONNECTOR PC46 AS
 EXISTING BEAM OVER 2X6 WALL SHOULD BE
 5 1/2" WIDE AND MAY NEED PC64
  
 7) ENERGY CALC'S SHALL BE SIGNED AND
 DATED BY OWNER AGENT
  
 8) SIMPSON WOOD CONNECTORS REQUIRE
 PRODUCT APPROVALS. FL STATE COVER SHEET
 WITH ALL CONNECTORS THAT WILL BE USED
 MARKED ON IT WILL BE OK (NO NOA'S WILL
 BE REQUIRED)
  
 9) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 WPB
 AMENDMENTS TO FBC 2004. (APPROVED BY
 ENGINEER ON DRAWINGS) STAMP APPROVED AND
 INITIAL
  
 NOTE: IF NEEDED CALL FOR CLARIFICATION
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  