| Notes |
| Date |
Text |
| 2005-12-29 00:00:00 | PLANS WERE OUT FRONT, BROUGHT BACK FOR | | | REVIEWS BY ELEC AND BLDG. | | | ********** UNSAT *********** | | | | | | | | | 1)NOTE: PLEASE SEE PLANS STATE THE 2001 | | | FBC , WHERE AS OF OCT. 1ST, 2005 THE | | | STATE ADOPTED THE NEW 2004 FBC. PLEASE | | | SEE BLDG REVIEW COMMENTS AS THIS WILL | | | AFFECT THE DESIGN. | | | | | | 2)NOTE: PLEASE SEE A PANEL SCHEDULE/LOAD | | | CALCULATIONS ARE SUBMITTED , HOWEVER | | | THESE DO NOT SEEM TO CORRELATE WITH THE | | | SINGLE CIRCUIT BEING ADDED. PLEASE SEE | | | LOAD OF 26A'S DOES NOT SEEM TO BE WHAT | | | THE NEW LOAD SHOULD BE AND IT DOES NOT | | | SEEM TO BE WHAT THE NEW AND EXISTING | | | LOADS SHOW BE?? | | | | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|