| 2005-12-29 00:00:00 | |
| | |
| | DENIED |
| | |
| | |
| | 1) PAY PALM BEACH COUNTY IMPACT FEES IF |
| | REQUIRED. HAVE BOTH SETS OF PLANS |
| | STAMPED AND A COPY OF THE RECEIPT FOR |
| | THE WEST PALM BEACH CONSTRUCTION |
| | SERVICES DEPT. |
| | |
| | 2) DRAWINGS AND SPECIFICATIONS SHALL |
| | COMPLY WITH THE 2004 FL BLDG CODE |
| | EFFECTIVE OCT.1, 2005. ADJUST |
| | REFERENCES, TABLES AND CODES ACCORDINGLY |
| | EG. WIND LOADS PER 1609, TABLES 1609A |
| | AND 1609B |
| | |
| | 3) CONNECTOR PC66 ON FOUNDATION PLAN IS |
| | FOR 6X6 POST SPEC THE CORRECT CONNECTOR |
| | FOR 4X6 POST |
| | |
| | 4) DETAIL 1/3 & 4/3 CALL FOR CONNECTOR |
| | HD2A DOES THIS APPLY TO DOUBLE STUDS AT |
| | DOOR AND WINDOW OPENINGS, IF SO PLEASE |
| | SPECIFY. ALSO DOES IT APPLY TO THE BUILT |
| | UP STUDS ON THE FOUNDATION PLAN WHERE |
| | THE NEW WALL BUTTS INTO EXISTING BLOCK |
| | WALL |
| | |
| | 5) SHOW DETAIL OF FRAMING AT DOOR AND |
| | WINDOW OPENINGS C/W CONNECTORS FOR STUD |
| | TO HEADER ATTACHMENT TO MEET WIND LOADS |
| | |
| | 6) INDICATE ON DRAWINGS ROOM THAT AJOINS |
| | NEW FAMILY ROOM ADDITION |
| | |
| | 7) PROVIDE 2 COPIES OF NEW ENERGY CALCS |
| | TO VERIFY EXISTING A/C UNIT ARE ABLE TO |
| | HANDLE THE EXTRA SQ FOOTAGE |
| | |
| | 8) PROVIDE 2 COPIES OF PRODUCT APPROVALS |
| | FOR ANY EXTERIOR BUILDING COMPONENT SUCH |
| | AS WINDOWS, SLIDING GLASS DOORS, STORM |
| | PANELS ETC THAT WILL BE USED IN |
| | CONSTRUCTION OF ADDITION. PRODUCT |
| | APPROVAL COVER SHEETS WITH FL#'S AND |
| | PRODUCT NOA'S CAN BE FOUND ON THE WEB |
| | SITE WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | BLDG PLAN REVIEW |