Plan Review Notes
Plan Review Notes For Permit 05110547
Permit Number 05110547
Review Stop P
Sequence Number 2
Notes
Date Text
2006-03-21 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED
  
 1)
 SEC 608.2 PLUMBING FIXTURES.
 THE WATER SUPPLY LINES FOR EVERY FIXTURE
 SHALL BE INSTALLEDSO AS TO PREVENT
 BACK FLOW.
 SEC 106.3.5.1.3 (4.)COMMERICAL
 BUILDINGS, PLUMBING SANITARY DRAINAGE.
 ( DWV ISOMETRIC ) REQUIRED
 PLUMBING RISER.
 SEPERATE THESANITARY WASTE, FROM WATER
 SUPPLY PIPING.
 2)
 NOTE: EXISTING WATER HEATER IS BEING
 REMOVED, SHOW NEW LOCATION, PROVIDE MFG
 INFORMATION, GAS OR ELECTRIC
 3)
 DETAIL STD GS-1
 NOTE 2: MAN HOLES LOCATED ON PRIVATE
 PROPRTY SHALL NOT HAVE " WEST PALM
 BEACH" EMBOSSED ON THEM.
 4)
 GREASE TRAP INLET AND OUTLET ARE
 LOCATED ON THE ENDS OF THE TANK, UNLESS
 SPECIAL ORDERED. PLEASE CLARIFI.
 5)
 BEVERAGE SERVICE AREA WASTE:
 PROVIDE A INDIRECT WASTE RECEPTOR.
 (FLOOR SINK)
 6)
 WASTE LINE SIZES, SEE TABLE 709.1 FOR
 FIXTURE DRAIN MINIMUM SIZE.
 7)ICE MACHINE DRAIN LINE, TO INDERICT
 WASTE RECEPTOR (FLOOR SINK)
  
 END OF COMMENTS, QUESTIONS 561-805-6692