| 2006-03-21 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | DENIED |
| | |
| | 1) |
| | SEC 608.2 PLUMBING FIXTURES. |
| | THE WATER SUPPLY LINES FOR EVERY FIXTURE |
| | SHALL BE INSTALLEDSO AS TO PREVENT |
| | BACK FLOW. |
| | SEC 106.3.5.1.3 (4.)COMMERICAL |
| | BUILDINGS, PLUMBING SANITARY DRAINAGE. |
| | ( DWV ISOMETRIC ) REQUIRED |
| | PLUMBING RISER. |
| | SEPERATE THESANITARY WASTE, FROM WATER |
| | SUPPLY PIPING. |
| | 2) |
| | NOTE: EXISTING WATER HEATER IS BEING |
| | REMOVED, SHOW NEW LOCATION, PROVIDE MFG |
| | INFORMATION, GAS OR ELECTRIC |
| | 3) |
| | DETAIL STD GS-1 |
| | NOTE 2: MAN HOLES LOCATED ON PRIVATE |
| | PROPRTY SHALL NOT HAVE " WEST PALM |
| | BEACH" EMBOSSED ON THEM. |
| | 4) |
| | GREASE TRAP INLET AND OUTLET ARE |
| | LOCATED ON THE ENDS OF THE TANK, UNLESS |
| | SPECIAL ORDERED. PLEASE CLARIFI. |
| | 5) |
| | BEVERAGE SERVICE AREA WASTE: |
| | PROVIDE A INDIRECT WASTE RECEPTOR. |
| | (FLOOR SINK) |
| | 6) |
| | WASTE LINE SIZES, SEE TABLE 709.1 FOR |
| | FIXTURE DRAIN MINIMUM SIZE. |
| | 7)ICE MACHINE DRAIN LINE, TO INDERICT |
| | WASTE RECEPTOR (FLOOR SINK) |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |