Plan Review Notes
Plan Review Notes For Permit 05110547
Permit Number 05110547
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-03 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 704 BELVEDER RD TULIPAN BAKERY
 561-820-6107
 DENIED
  
 SEC106.1.1 PLANS REQUIRED
 (1) SITE PLAN, SHOW BUILDING FOOT
 PRINT,LOCATION OF THE 750 GALLON GREASE
 TANK.
 (2) SHOW DRAIN LINE PIPING, CLEAN OUT ON
 INLET AND OUT LET OF TANK.
 (3) PROVIDE A ISOMETRIC DRAWING OF THE
 GREASE WASTE SYSTEM.
 ALL INDIRECT WASTE TO FLOOR SINKS.
 CAN WASH AND LOCATION.
 (4) ALL FLOOR DRAINS IN FOOD PREPARATION
 AREA TO GREASE WASTE.
 SHOW LOCATION OF THREE COMPARTMENT SINK.
  
 (5) GREASE TRAP SIZE
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
  
 OFFICE 561-822-2271E-MAIL
 [email protected]
 (6) WATER HEATER LOCATED OUT SIDE: SHALL
 HAVE A WEATHER PROTECTION ENCLOSER.
 END OF COMMENTS QUESTIONS 561-805-6692