| 2007-06-03 16:28:33 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING DISCONNECT FOR MASTER |
| | BEDROOM WATER HEATER.422.31 THE SYMBOL AS SHOWN ON |
| | PLANS IS FOR A RECEPTACLE. |
| | |
| | 2) NOTE: PLEASE SEE PANEL SCHEDULES WHICH INDICATE TWO |
| | AHU'S #2. PLEASE SEE PANEL *B* WHICH INDICATE 10KW AHU |
| | WITH 30AMP OCP AND #8 CONDUCTORS WHICH ARE NOT OF |
| | SUFFICIENT SIZE PER 240.4, 424.3B, AND 310.16. |
| | PLEASE ADJUST. |
| | |
| | 4) NOTE: PLEASE SEE PANEL SCHEDULES STILL INDICATE 40 |
| | CIRCUITS( MISPRINT). |
| | PLEASE ADJUST. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE PROVIDE THE GROUNDING ATTACHMENT FOR |
| | THE DETACHED GARAGE AS REQUIRED PER 250.32. THIS WAS |
| | ISSUED WITH NOTE ON PLAN TO COMPLY, HOWEVER THE |
| | ATTACHMENT SHOULD BE KNOWN AND SHOWN ON PLANS. |
| | |
| | 6) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE |
| | SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| | SMOKE DETECTORS. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY |
| | THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |