| Date |
Text |
| 2006-01-30 00:00:00 | ******** UNSAT2ND REVIEW ********** |
| | |
| | PLEASE SEE SOME EXISTING NOTES AND SOME |
| | NEW NOTES. |
| | |
| | |
| | |
| | 1)NOTE: OK |
| | |
| | 2)NOTE: OK |
| | |
| | 3)NOTE: OK, HOWEVER PLEASE NOW SEE POOL |
| | HEATER IS BEING SHOWN AS GAS, YET SHOWS |
| | 4KW LOAD AND SHOWS BEING CONTINUOUS?? |
| | PREVIOUS PLANS CALLED FOR AN ELEC HEAT |
| | PUMP. |
| | |
| | ** PLEASE INDICATE ALL CONTINUOUS |
| | LOADS ON POOL PANEL AT 125%. |
| | PLEASE ALSO SEE THIS WILL CHANGE LOAD |
| | AND EXCEED RATING OF OCP AND FEEDERS TO |
| | POOL PANEL. PLEASE ADJUST AS NEW OCP AND |
| | FEEDERS WILL NEED TO BE INCREASED. |
| | 215.5,230.42,215..3,90.8 |
| | |
| | 4)NOTE: OK |
| | |
| | 5)NOTE: OK |
| | |
| | 6)NOTE: OK |
| | |
| | 7)NOTE: OK, HOWEVER PLEASE SEE |
| | DISCONNECTING NOTE FOR DETACHED GARAGE. |
| | |
| | 8)NOTE: OK |
| | |
| | 9)NOTE: OK |
| | |
| | 10)NOTE: OK, NOTED. |
| | |
| | 11)NOTE:OK/ NO, PLEASE SEE DISCONNECT |
| | SWITCH(S) SHOULD BE SHOWN FOR GDO NOW |
| | ADDED. |
| | PLEASE SEE NOTE ADDED FOR GROUNDING, |
| | SHOULD REFERENCE 250.32, HOWS 225.31 |
| | WHICH IS THE DISCONNECT REQUIREMENT. |
| | PLEASE SEE 250.32 WHICH REQUIRES A |
| | GROUNDING ELECTRODE TO FOOTER STEEL MIN |
| | . |
| | |
| | **PLEASE SEE THE DETACHED GARAGE |
| | WOULD REQUIRE MEANS OF DISCONNECT AS |
| | REQUIRED UNDER 225.31-225.36. |
| | PLEASE SEE DISCONNECTING MEANS MAY BE A |
| | TOGGLE SWITCH TYPE DEVICE IF MEETING THE |
| | EXCEPTIONS. |
| | |
| | 12)NOTE: OK |
| | |
| | 13)NOTE: NO, PLEASE SEE PANEL "A" SHOWS |
| | A 5KW HEAT, LOAD CALCULATIONS INDICATE |
| | 65% AS 6500W?? |
| | PLEASE ALSO SEE PANEL "B" SHOWS TWO |
| | UNITS AS 10KW, HOWEVER 65% ON LOAD |
| | CALCUALTIONS INDICATES 9750W?? |
| | PLEASE SEE 655 OF 20KW ,, |
| | PLEASE CORRELATE ALL KW LOADS |
| | FOR AHU'S WITH KW RAITNGS SHOWN ON |
| | MECHANICAL PLANS. PLEASE MAKE ANY |
| | ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD |
| | CALCS ETC. |
| | 215.5 |
| | |
| | NEW NOTES: |
| | |
| | 1)NOTE: PLEASE SEE POOL PANEL IS SHOWN |
| | ON PLANS BEING FED FROM WHAT APPEARS TO |
| | BE THE INSIDE PANEL "B", YET RISER SHOWS |
| | THIS COMING FROM THE OUTSIDE MCB PANEL. |
| | ?? |
| | ** PLEASE CORRELATE RISER AND PANELS AS |
| | PANEL SCHEDULES SHOWN INDICATE THESE AS |
| | MCB PANELS WHICH ARE 40 CIRCUIT PANELS, |
| | YET RISER SHOWS THE MCB PANELS AS 8-16? |
| | PLEASE ALSO SEE RISER AS THESE PANELS DO |
| | NOT SEEM TO CORRELATE. |
| | ** PLEASE PROVIDE PANEL SCHEDULES FOR |
| | OUTDOOR MCB PANELS IF THERE ARE CIRCUITS |
| | COMING FROM THESE PANELS AS SHOWN. |
| | ** PLEASE SEE 230.7, SERVICE ENTRANCE |
| | CONDUCTORS MAY NOT BE IN THE SAME |
| | RACEWAY/ENCLOSURE WITH THE |
| | BRANCHCIRCUITS OR FEEDERS. |
| | PLEASE REVISE RISER DIAGRAM AS MCB PANEL |
| | "B" MAY NOT BED FED THORUGH MCB PANEL |
| | "A". |
| | |
| | 2)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND REPEAT COMMENTS FOR |
| | CODE COMPLIANCE. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM PLANS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. |
| | ONE COPYOF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER REVIEWS WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |