| 2005-12-07 00:00:00 | ******** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE ELECTRICAL PLANS DO |
| | NOT CORRELATE WITH BLDG PLANS/A-SHEETS. |
| | PLEASE SEE THESE ARE TWO COMPLETELY |
| | DIFERENT HOUSES. |
| | PLEASE ADJUST. |
| | PLEASE VERIFY WHAT APPEARS TO BE A |
| | CLOSET OF SOME SORT IN WALK IN CLOSET OF |
| | MASTER BEDRM AREA THAT APPEARS TO SHOW A |
| | WATER HEATER?? |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM MAINS TO SUB |
| | PANEL(S) A AND B. |
| | 250.110,250.122 |
| | |
| | 3)NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS ON POOL PANEL AT 125%. |
| | PLEASE ALSO SEE THIS WILL CHANGE LOAD |
| | AND EXCEED RATING OF OCP AND FEEDERS TO |
| | POOL PANEL. PLEASE ADJUST AS NEW OCP AND |
| | FEEDERS WILL NEED TO BE INCREASED. |
| | 215.5,230.42,215..3,90.8 |
| | |
| | 4)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. PLEASE SEE ONE SET OF PLANS HAVE |
| | BEEN REDLINED WITH MANY OF THESE |
| | LOCATIONS INDICATED. |
| | |
| | 5)NOTE: PLEASE SEE RECEPT MISSING PER |
| | 210.52H FOR HALLWAY. 10' OR MORE OF |
| | WALL. |
| | |
| | 6)NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.52E, FRONT GFI. |
| | |
| | 7)NOTE: PLEASE CORRELATE THE # OF GDO |
| | CIRCUITS ON PANEL SCHEDULE WITH THE |
| | ACTUAL # NEEDED ON PLANS. PLEASE SEE |
| | OTHER GARAGE. |
| | PLEASE ALSO SEE PLANS DO NOT INDICATE |
| | ANY RECEPTS AT THESE LOCATIONS. |
| | 215.5, 430.24. TABLES). |
| | |
| | 8)NOTE: PLEASE SEE DISC'S FOR A/C CU |
| | UNITS SHALL MEET 110.26 |
| | |
| | 9)NOTE: PLEASE SEE NFPA -72 11-8.3.5 |
| | WHICH REQUIRES ALL SD'S TO BE INSTALLED |
| | WITH-IN 12" OF A FLAT CEILING AREA. |
| | PLEASE SEE "TRAY" CEILING AREA WOULD |
| | REQUIRE TO THESE SD'S LOCATED AT THESE |
| | AREAS IF HEY ARE 12" OR MORE HIGHER THAN |
| | SURROUNDING CEILING AREA. SEE REDLINED |
| | PLANS. |
| | |
| | 10)NOTE: PLEASE SEE 410.8 FOR TYPE OF |
| | FIXTURE AND MIN CLEARENCES PERMITTED |
| | ABOVE TUB/WHIRLPOOL. PLEASE PLACE NOTE |
| | ON PLANS AS THIS IS SHOWN AS A "J-BOX" |
| | FOR FUTURE. |
| | |
| | 11)NOTE: PLEASE SEE THE DETACHED GARAGE |
| | WOULD REQUIRE MEANS OF DISCONNECT AS |
| | REQUIRED UNDER 225.31-225.36. |
| | PLEASE SEE DISCONNECTING MEANS MAY BE A |
| | TOGGLE SWITCH TYPE DEVICE IF MEETING THE |
| | EXCEPTIONS. |
| | |
| | 12)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | RECESSED LTS ON PANEL LOAD CALCULATIONS |
| | WITH THE # OF FIXTURES ON PLANS. |
| | 215.5,220.3B4 |
| | |
| | 13)NOTE: PLEASE CORRELATE ALL KW LOADS |
| | FOR AHU'S WITH KW RAITNGS SHOWN ON |
| | MECHANICAL PLANS. PLEASE MAKE ANY |
| | ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD |
| | CALCS ETC. |
| | 215.5 |
| | |
| | ** PLEASE KNOW, DEPENDING ON POSSIBLE |
| | CHANGES IN "HOUSE PLANS" OR LAYOUT NOT |
| | ALL COMMENTS MAY BE ON THIS REVIEW IF |
| | THIS CHANGE OCCURS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM PLANS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. |
| | ONE COPYOF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER REVIEWS WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |