| Plan Review Notes For Permit 05110482 |
| Permit Number |
05110482 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-01 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | CHANGE OF OCCUPANCY. SHALL BRING UP TO | | | CODE FOR BUSINESS OCCUPANCY. | | | | | | 1. SUBMIT CALCULATIONS FOR MINIMUM | | | FIXTURE REQUIREMENTS PER TABLES 1004.1.2 | | | AND 403.1. | | | | | | 2. SHOW THE LOCATION FOR ALL REQUIRED | | | FIXTURES AND ALL EXISTING FIXTURES. | | | TABLES 1004.1.2 & 403.1. | | | | | | 3. SUBMIT A DETAIL FOR THE REQUIRED | | | FIXTURES SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.15, 11-4.16, 11-4.19 AND | | | ALL SUBSECTIONS. IF THERE ARE ANY SINKS | | | SUBMIT A DETAIL SHOWING COMPLIANCE WITH | | | 11-4.24 AND ALL SUBSECTIONS. | | | | | | 4. AN RPZV BACKFLOW IS REQUIRE ON THE | | | WATER SERVICE TO THE BUILDING. SECTION | | | 608. | | | | | | 5. IF ANY PLUMBING PIPING WILL BE DONE | | | SUBMIT SANITARY AND WATER RISER DIARAMS. | | | SECTION 106.3.5.1.3 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | 2006-06-30 00:00:00 | CHANGE IN USE FROM SFR TO COMM OFFICE. |
|