Date Text
2006-08-01 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 CHANGE OF OCCUPANCY. SHALL BRING UP TO
 CODE FOR BUSINESS OCCUPANCY.
  
 1. SUBMIT CALCULATIONS FOR MINIMUM
 FIXTURE REQUIREMENTS PER TABLES 1004.1.2
 AND 403.1.
  
 2. SHOW THE LOCATION FOR ALL REQUIRED
 FIXTURES AND ALL EXISTING FIXTURES.
 TABLES 1004.1.2 & 403.1.
  
 3. SUBMIT A DETAIL FOR THE REQUIRED
 FIXTURES SHOWING COMPLIANCE WITH
 SECTIONS 11-4.15, 11-4.16, 11-4.19 AND
 ALL SUBSECTIONS. IF THERE ARE ANY SINKS
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 11-4.24 AND ALL SUBSECTIONS.
  
 4. AN RPZV BACKFLOW IS REQUIRE ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.
  
 5. IF ANY PLUMBING PIPING WILL BE DONE
 SUBMIT SANITARY AND WATER RISER DIARAMS.
 SECTION 106.3.5.1.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
2006-06-30 00:00:00CHANGE IN USE FROM SFR TO COMM OFFICE.