Plan Review Notes
Plan Review Notes For Permit 05110474
Permit Number 05110474
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-12-07 00:00:001. REQUIRED SMOKE MANAGEMENT SYSTEM IS
 TO BE CONNECTED TO EMERGENCY POWER.
  
 2. SYSTEM IS TO CONFORM TO NFPA 92B AND
 NFPA 101, 2003 EDITION SECTION 8.6.7.
  
 3. A TIME EGRESS ANALYSIS REPORT IS TO
 BE SUBMITTED TO THIS OFFICE.
  
 4. WHEN COMPLETED THE SYSTEM IS TO BE
 FULLY TESTED WITH MECHANICAL AND FIRE
 RESCUE DEPARTMENTS.
  
 5. SOME SMOKE BOMBS WILL BE NEEDED TO
 PERFORM THE TEST TO ENSURE PROPER
 OPERATION.
  
 6. ATRIUM SMOKE SYSTEM SHALL BE
 INITIATED BY THE FIRE ALARM SYSTEM OR BY
 THE FIREFIGHTERS SMOKE PANEL. HOA
 SWITCHES ONLY WILL NOT BE PERMITTED TO
 BE USED. A GRAPHIC REPRESENTATION OF THE
 ATRIUM SHALL BE SHOWN ON THIS PANEL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER