| Plan Review Notes For Permit 05110474 |
| Permit Number |
05110474 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-07 00:00:00 | 1. REQUIRED SMOKE MANAGEMENT SYSTEM IS | | | TO BE CONNECTED TO EMERGENCY POWER. | | | | | | 2. SYSTEM IS TO CONFORM TO NFPA 92B AND | | | NFPA 101, 2003 EDITION SECTION 8.6.7. | | | | | | 3. A TIME EGRESS ANALYSIS REPORT IS TO | | | BE SUBMITTED TO THIS OFFICE. | | | | | | 4. WHEN COMPLETED THE SYSTEM IS TO BE | | | FULLY TESTED WITH MECHANICAL AND FIRE | | | RESCUE DEPARTMENTS. | | | | | | 5. SOME SMOKE BOMBS WILL BE NEEDED TO | | | PERFORM THE TEST TO ENSURE PROPER | | | OPERATION. | | | | | | 6. ATRIUM SMOKE SYSTEM SHALL BE | | | INITIATED BY THE FIRE ALARM SYSTEM OR BY | | | THE FIREFIGHTERS SMOKE PANEL. HOA | | | SWITCHES ONLY WILL NOT BE PERMITTED TO | | | BE USED. A GRAPHIC REPRESENTATION OF THE | | | ATRIUM SHALL BE SHOWN ON THIS PANEL. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|