| 2005-12-01 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05110469 |
| | ADD: 515 N FLAGLER # 300 |
| | CONT: SUFFOLK |
| | TEL: (561)832-1616 |
| | FL BLD CODE= 200$ FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1)110.2 REQUIREMENTS OF THE 2004 FOR |
| | C.O. AND FOR RECORD KEEPING PURPOSES |
| | REQUIRES : |
| | 1A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | 1B) THE USE & OCCUPANCY IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | 1C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6. |
| | 1D) THE DESIGN OCCUPANT LOAD. |
| | 1E) IF AN AUTOMATIC FIRE SPREINKLER |
| | SYSTEM IS PROVIDED , WHETHER THE |
| | SPRINKLER SYSTEM IS REQUIRED. |
| | 1F) ANY SPECIAL STIPULATIONS & |
| | CONDITIONS OF THE BUILDING PERMIT. |
| | |
| | 2) CORRECT THE BUILDING TYPE AND |
| | REFRENCE TO TABLE 600. SEE TABLE 601 |
| | FIRE RESITANCE REQUIREMENTS FOR BUILDING |
| | ELEMENTS. |
| | |
| | 3) TI-1 DOOR BUCKS TO BE |
| | 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED |
| | IN BUILDINGS OF TYPE I OR II |
| | CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH |
| | SECTIONS 603.1.1 THROUGH 603.1.3 : |
| | 1.FIRE-RETARDANT-TREATED WOOD SHALL |
| | BE PERMITTED IN: |
| | 1.1.NONBEARING PARTITIONS WHERE THE |
| | REQUIRED FIRE-RESISTANCE RATING IS 2 |
| | HOURS OR LESS. |
| | 1.2.NONBEARING EXTERIOR WALLS WHERE |
| | NO FIRE RATING IS REQUIRED. |
| | 1.3.ROOF CONSTRUCTION AS PERMITTED |
| | IN TABLE 601 , NOTE C, ITEM 3. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |