2006-04-07 00:00:00DENIED;
 1.PLANS ARE NOT SEALED OR SIGNED.
 2.PLUMBING NOTES REMOVE NOTE ABOUT SAFE
 WASTE OF CONDENSATE. CONDENSATE DISPOSAL
 IS NOT PERMITED TO DUMP INTO CITY SEWER.
 SEE FBC-2004 MECHANICAL SEC. 307 FOR
 APPROVED DISPOSAL .
 3.RISER DIAGRAM SHOWER NOT VENTED AS
 SHOWN, ADD TRAP TO SHOWER.
 4.AUTOMATIC CLOTHES WASHER DRAIN SHALL
 CONNECT TO A 3" BRANCH DRAIN. SEC. 406.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695