| Plan Review Notes For Permit 05110448 |
| Permit Number |
05110448 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-06 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS ARE CALLING FOR A | | | 5 KW HEATER, AND THE ELECTRICAL PLANS | | | ARE CALLING FOR A 10 KW HEATER. THE | | | PLANS CAN NOT CALL FOR MORE THAN THE | | | ENERGY CAL'S.,PLEASE CORRECT. | | | | | | 2) PLEASE SHOW ELECTRICAL HEATER SIZE ON | | | MECHANICAL PLANS. | | | | | | 3) PLEASE SHOW THE TERMINATION POINT OF | | | THE CLOTHES DRYER VENT ON THE MECHANICAL | | | PLANS. PLEASE SEE 2004 FBC/M 502.7.3.6 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|