| Notes |
| Date |
Text |
| 2006-01-09 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LOAD CALCULATIION MUST BE PER 220 | | | SECTION II OR 220 SECTION III. PLEASE | | | RESUBMIT AND INDICATE THE ARTICLE BEING | | | USED, FOR EXAMPLE 220.30. SEE 215.5. | | | | | | 2} RECEPTACLES MUST BE ADDED TO THE NEW | | | BEDROOM TO COMPLY WITH 210.52(A)(1), SEE | | | REVIEWED SET.. | | | | | | 3} A SMOKE DETECTOR MUST BE LOCATED IN | | | THE BEDROOM PER 313.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|