Plan Review Notes
Plan Review Notes For Permit 05110448
Permit Number 05110448
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIION MUST BE PER 220
 SECTION II OR 220 SECTION III. PLEASE
 RESUBMIT AND INDICATE THE ARTICLE BEING
 USED, FOR EXAMPLE 220.30. SEE 215.5.
  
 2} RECEPTACLES MUST BE ADDED TO THE NEW
 BEDROOM TO COMPLY WITH 210.52(A)(1), SEE
 REVIEWED SET..
  
 3} A SMOKE DETECTOR MUST BE LOCATED IN
 THE BEDROOM PER 313.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  