Plan Review Notes
Plan Review Notes For Permit 05110390
Permit Number 05110390
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-06 00:00:00********* UNSAT ***********
  
  
 1)NOTE: PLEASE CORRECT PLANS FOR
 ADDRESSINGAND STATION IN WHICH WORK IS
 BEING DONE.
 PLEASE KNOW, THE STATION LOCATED AT 500
 N. DIXIE, IS FIRE STATION #1.
 PLEASE ADJUST PAPERWORK AS NEEDED.
 ** PLEASE ALSO SEE THE SITE/ELEVATION
 PLANS SUBMITTED INDICAT THE STATION
 LOCATED OFF CUMBERLAND DR??
 PLEASE CORRELATE ALL PAPERWORK FO THE
 JOBSITE LOCATION IN WHICH WORK IS BEING
 PERFORMED.
  
 2)NOTE: PLEASE PROVIDE PLANS TO BE DONE
 MINIMUM BY AN ARCHITETC AS REQUIRED
 UNDER FS 481.229. PLANS MAY ALSO BE DONE
 BY AND PE AS LISTED UNDER FS
 471.003(2)H).
 PLEASE SEE THE FOLLOWING COMMENT AS
 PLANS MAY BE REQUIRED TO BE DONE BY A PE
 AS VALUE MAY BE ADJUSTED. (IF $50K OR
 MORE, THEN A PE WILL BE REQUIRED FOR
 PLANS.
  
 3)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH REQUIRES VALUE BASED
 ON COMPLETE SCOPE WORK TO INCLUDE ALL
 LABOR AND MATERIALS, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED.
 PLEASE SEE VALUE IS SHOWN AS THE SAME
 FOR ALL THREE PERMITTED JOBS.
  
 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR THE NEW GENERATOR,
 ATS AND FUEL TANK.
 215.5
  
 5)NOTE: PLEASE SEE NFPA-209.6.2.2
 WHICH REQUIRED A MIN OF 8HRS FUEL SUPPLY
 FOR FIRE PUMP (IF APPLICABLE). IT IS NOT
 KNOW IF THIS BLDG CONTAIN ANY FIRE PUMP.
 PLEAS PROVIDE MIN FUEL FOR ALL LIFE
 SAFETY DEVICES.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS.
  
 6)NOTE: PLEASE SEE ATS IS SHOWN WITH AN
 EQUIPMENT GROUNDING CONDUCTOR FROM ATS
 TO GUTTER, ? PLEASE VERIFY IF THERE IS A
 MAIN LOCATED ON THE LINE SIDE OF OF THIS
 ATS. PLEASE SEE 250.24, 250.6
 THE GROUNDING OF ELECTRICAL SYSTEMS,
 CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND
 CONDUCTIVE NON?CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE
 INSTALLED AND ARRANGED IN A MANNER THAT
 WILL PREVENT OBJECTIONABLE CURRENT OVER
 THE GROUNDING CONDUCTORS OR GROUNDING
 PATHS.
  
 7)NOTE: PLEASE DECLARE WHETHER OR NOT
 THE GENERATOR WILL OR WILL NOT BE A
 SEPARATEY DERVIED SYSTEM. PLEASE ADJUST
 AS NEEDED.
 215.5
  
 8)NOTE: PLEASE SEE 445.13 FOR MIN SIZING
 OF CONDUCTORS FROM GENERATOR TO ATS,
 FIRST MEANS OF OCP.
 215.5, 240.4,310.16
  
 9)NOTE: PLEASE SEE NO OCP IS SHOWN AT
 GENERATOR.?
 215.5
  
 10)NOTE: PLEASE SUBMIT PLANS INDICATION
 LOCATION OF GENERATOR AT SITE.
 PLEASW SHOW DETAIL OF WHERE BOLLARDS MAY
 BE REQUIRED DEPENDING ON THE LOCATION OF
 GENERATOR ETC.
  
 11)NOTE: PLEASE SEE BLDG REVIEW ,AS NO
 SLAB/FOOTER DETAILS WERE SUBMITTED.
  
 12)NOTE: PLEASE SEE EXISTING GROUNDING
 ELECTRODE LOCATION IS BEING SHOWN AT CT
 CAN, PLEASE VERIFY.
 250.24.
  
 13)NOTE: PLEASE SEE NO OCP IS INDICATED
 FOR NEW FEED TO PANEL EM?
 CAN NOT VERIFY FEEDERS ETC AT THIS TIME.
 215.5,310.16
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY
 QUESTIONS,PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
 PLANS GIVEN ABCK TO LUIS M.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved