| Plan Review Notes For Permit 05110342 |
| Permit Number |
05110342 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-09 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE CITY OF WEST PALM BEACH HAS | | | ADOPTED A POLICY FOR GENERATORS THAT IS | | | ATTACHED. THE LOAD CALCULATION MUST BE | | | DERIVED FROM 220.31. | | | | | | 2} PLEASE SUBMIT A SITE PLAN SHOWING THE | | | LOCATION OF ALL SERVICE AND GENERATOR | | | EQUIPMENT SO THAT COMPLIANCE WITH | | | 225.31-39 CAN BE DETERMINED. | | | | | | THE PERMIT VALUE MUST INCLUDE THE COST | | | OF ALL LABOR AND MATERIAL IF APPLYING | | | FOR A GEN RES PERMIT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|