| Plan Review Notes For Permit 05110320 |
| Permit Number |
05110320 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | ********* UNSAT ********** | | | | | | | | | 1)NOTE: PLEASE CORRELATE NEW | | | CONDUCTOR/FEEDER SIZES FROM PANEL "6HB" | | | TO NEW 45KVA TRANSFORMER. PLEASE SEE | | | RISER SHOWS 1/0'S AND PANEL SCHEDULE | | | SHOWS #4. | | | | | | | | | 2)NOTE: PLEASE SHOW GROUNDING FOR | | | TRANSFORMER PER 250.30 FOR SEPARATELY | | | DERIVED SYSTEMS. | | | PLEASE ALSO SEE 250.66 FOR SIZING. | | | | | | PLEASE SEE PLANS ARE COMING BACK, PLEASE | | | MAKE THE ABOVE CORRECTIONS AT THIS TIME. | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS | | | AND ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETED SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD VOIDED SHEETS SHOULD BE | | | SUBMITTED FOR REFERENCE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|