| Plan Review Notes For Permit 05110306 |
| Permit Number |
05110306 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-11-06 09:39:24 | PROVISO: | | | PLANS DO NOT INDICATE RETURN AIR DUCTS NEW / EXISTING | | | OR ANNOTATE THE CEILING AS A RETURN AIR PLENUM.PER | | | 2004 FMC 601.4, BALANCED RETURN REQUIRED. SHOULD THE | | | CEILING AREA BE A RETURN AIR PLENUM, NO COMBUSTIBLES | | | ALLOWED IN THE RETURN AIR PLENUM IN ACCORDANCE WITH | | | 2004 FMC 602.2.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|