2006-12-19 18:16:08REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT P-1.AS INDICATED ON PREVIOUS REVISION REVIEW,
 MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO SEE. THE
 REVISION FOR NUMBER 5 IS FAINT & HARD TO SEE. A NEW
 REVISION WAS FOUND ON THE PLAN. THIS NUMBER 6 REVISION
 IS NOT CLOUDED AND NOT INDICATED IN THE REVISION INDEX.
 PLEASE CLOUD ALL REVISIONS WITH A HEAVY CLOUD, AND SHOW
 ALL REVISIONS ON THE REVISION INDEX.
  
 2. SHT P-5. REVISION #6 NOT CLOUDED. PLEASE CLOUD ALL
 REVISIONS. IT APPEARS THAT THERE IS A NEW TOILET ROOM.
 IF SO PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SUBMIT A REVISION FOR THE SANITARY RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN, SHOWING THE NEW
 TOILET ROOM PIPING AND INDICATING ALL PIPE SIZES,
 TRAPS, VENTS ETC. SECTION 106.3.5.1.3.
  
 3. SHT P-8REVISION 5 NOT SHOWN ON THE REVISION INDEX,
 NOR IS THE REVISION CLOUDED. PLEASE CLOUD ALL REVISIONS
 AND INDICATED THE REVISION NUMBER ON THE REVISION
 INDEX. SECTION 106.1.1. - REVISION 3 IS NOT CLOUDED,
 NOR DOES IT INDICATE WHAT CHANGE HAS BEEN MADE. PLEASE
 CLARIFY. SECTION 106.1.1.
  