| Plan Review Notes For Permit 05110263 |
| Permit Number |
05110263 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-12-19 18:16:08 | REVISION DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT P-1.AS INDICATED ON PREVIOUS REVISION REVIEW, | | | MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO SEE. THE | | | REVISION FOR NUMBER 5 IS FAINT & HARD TO SEE. A NEW | | | REVISION WAS FOUND ON THE PLAN. THIS NUMBER 6 REVISION | | | IS NOT CLOUDED AND NOT INDICATED IN THE REVISION INDEX. | | | PLEASE CLOUD ALL REVISIONS WITH A HEAVY CLOUD, AND SHOW | | | ALL REVISIONS ON THE REVISION INDEX. | | | | | | 2. SHT P-5. REVISION #6 NOT CLOUDED. PLEASE CLOUD ALL | | | REVISIONS. IT APPEARS THAT THERE IS A NEW TOILET ROOM. | | | IF SO PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND ALL | | | SUBSECTIONS. SUBMIT A REVISION FOR THE SANITARY RISER | | | DIAGRAM THAT REFLECTS THE FLOOR PLAN, SHOWING THE NEW | | | TOILET ROOM PIPING AND INDICATING ALL PIPE SIZES, | | | TRAPS, VENTS ETC. SECTION 106.3.5.1.3. | | | | | | 3. SHT P-8REVISION 5 NOT SHOWN ON THE REVISION INDEX, | | | NOR IS THE REVISION CLOUDED. PLEASE CLOUD ALL REVISIONS | | | AND INDICATED THE REVISION NUMBER ON THE REVISION | | | INDEX. SECTION 106.1.1. - REVISION 3 IS NOT CLOUDED, | | | NOR DOES IT INDICATE WHAT CHANGE HAS BEEN MADE. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|