Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop P
Sequence Number 6
Notes
Date Text
2006-11-01 14:01:13REVISIONDENIED
 REFERENCE:
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P-1, P-5, P-8 PLUMBING TECHNICAL CODES OK, BUT
 THE TITLE BLOCK FOR THE ARCHITECT DOES NOT HAVE THE
 REQUIRED BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IN THE TITLE BLOCK. THIS HAS BEEN
 COMMENTED ON SINCE FEB. 06 IN THE FIRST PLAN REVIEW FOR
 PLUMBING. EIGHT MONTHS IS SUFFICIENT TIME TO APPLY FOR
 A CERTIFICATE OF AUTHORIZTION. EITHER REMOVE "GRW
 ARCHITECTS" FROM THE SHEETS, OR INDICATE THE BUSINESS
 NUMBER IN THE TITLE BLOCK AS REQUIRED IN FAC
 61G1-16.004(2) & FS 481.219.
  
 2. WHEN RESUBMITTING REVISIONS, DISABLE ALL REVISION
 CLOUDS FROM PREVIOUS REVISIONS AND ONLY SHOW THE
 CLOUDED REVISIONS BEING SUBMITTED FOR THE PRESENT
 REVISION. ALSO MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO
 SEE. THE LAST REVISIONS WERE DIFFICULT TO FIND. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]