| Plan Review Notes For Permit 05110263 |
| Permit Number |
05110263 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-11-21 09:59:48 | DENIED: | | | REVISED SHEET M-1 IS MISSING FIRE DAMPERS IN THE | | | FOLLOWING AREAS: | | | | | | 1.SUPPLY & RETURN AIR DUCTS FROM AHU-3, PLAN SHEET | | | A.01 INDICATES MECHANICAL CLOSET HAS A 1 HR RATING, | | | FIRE DAMPERS ARE REQUIRED. | | | | | | 2.S/A & R/A FROM AHU-3 INTO THE CORRIDOR AREA AND | | | DUCTS PENETRATING INTO THE FOLLOWING ROOMS;47,48, 46, | | | 50, 51, PLEASE NOTE, PER 2004 FMC 603.5.5, FLEXIBLE AIR | | | DUCTS & FLEX CONNECTORS SHALL NOT PASS THROUGH ANY | | | FIRE-RESISTANCE-RATED ASSEMBLY.PLANS INDICATE FLEX | | | DUCT PENETRATING RATED CORRIDOR.PLEASE ALSO SEE | | | EXCEPTIONS IN 607.5.3, SHOULD PENETRATIONS COMPLY WITH | | | THE AFOREMENTIONED SECTION, PLEASE ANNOTATE THIS | | | SECTION ON THE PLAN. | | | | | | 3. PLEASE CLARIFY THE PENETRATION BETWEEN THE GUEST | | | LAUNDRY ROOM AND THE LOCKER AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected] | | | | | | *****************REVIEW IN | | | PROGRESS************************ |
|