Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop M
Sequence Number 4
Notes
Date Text
2006-11-21 09:59:48DENIED:
 REVISED SHEET M-1 IS MISSING FIRE DAMPERS IN THE
 FOLLOWING AREAS:
  
 1.SUPPLY & RETURN AIR DUCTS FROM AHU-3, PLAN SHEET
 A.01 INDICATES MECHANICAL CLOSET HAS A 1 HR RATING,
 FIRE DAMPERS ARE REQUIRED.
  
 2.S/A & R/A FROM AHU-3 INTO THE CORRIDOR AREA AND
 DUCTS PENETRATING INTO THE FOLLOWING ROOMS;47,48, 46,
 50, 51, PLEASE NOTE, PER 2004 FMC 603.5.5, FLEXIBLE AIR
 DUCTS & FLEX CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE-RESISTANCE-RATED ASSEMBLY.PLANS INDICATE FLEX
 DUCT PENETRATING RATED CORRIDOR.PLEASE ALSO SEE
 EXCEPTIONS IN 607.5.3, SHOULD PENETRATIONS COMPLY WITH
 THE AFOREMENTIONED SECTION, PLEASE ANNOTATE THIS
 SECTION ON THE PLAN.
  
 3. PLEASE CLARIFY THE PENETRATION BETWEEN THE GUEST
 LAUNDRY ROOM AND THE LOCKER AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected]
  