Plan Review Notes
Plan Review Notes For Permit 05110263
Permit Number 05110263
Review Stop P
Sequence Number 3
Notes
Date Text
2006-07-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WPB CITY CODE/ORDINENCES
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS WILL REMAIN THE SAME.
  
 5. SHT A.01 ROUTE PLANS TO DBPR,
 DIVISION OF HOTEL & RESTURANT FOR REVIEW
 PRIOR TO RESUBMITTING. MINIMUM 3 SETS OF
 PLANS SHALL BE REVIEWED, STAMPED AND TWO
 SHEET "WORKSHEETS" SHALL BE ATTACHED TO
 EACH SET OF PLANS SUBMITTED FOR REVIEW.
 SECTION 102.2.1.
 ***NO RESPONSE, NOT ADDRESSED.
 ***RESPONSE NOTED, BUT NEW SHEETS SHALL
 BE INSERTED INTO THE PLANS, AND ALL
 VOIDED SHEETS REMOVED. ATTACH 2 PAGE
 "SPECIFICATION WORKSHEETS" TO EACH SET
 OF PLANS. REMOVE BUSINESS NAME FROM THE
 TITLE BLOCK, OR INDICATE CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCK. THE
 SIGNED SEALED SHALL BE DATED WHEN SEAL
 IS AFFIXED TO DRAWINGS. FAC 61G1-16.003
 & 61G1-16.004(5) - FS 481.219.
  
 10. SHT A.01 ADA ROOMS MATRIX INDICATES
 5 ROOMS FOR THE HEARING IMPAIRED ROOMS.
 ONE ROOM (226) IS NOT SHOWN ON THE FLOOR
 PLAN. (4 OTHER ROOMS SHOWN AS HEARING
 IMPAIRED ACCOMODATIONS). PLEASE CLARIFY.
 SECTION 11-9.1.3.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT HEARING IMPAIRED
 ROOMS SHALL BE IN ADDITION TO THOSE
 ACCESSIBLE SLEEPING ROOMS AND SUITES
 REQUIRED BY 11-9.1.2. ONLY ROOMS 307 &
 407 MEET THIS REQUIREMENT. 2 OTHER
 HEARING IMPAIRED ACCOMMODATION ROOMS
 REQUIRED.
  
 11. SHT A.01 1 ROOM SHALL COMPLY WITH
 SECTION 11-9.2.3 PLEASE INDICATE THE
 ROOM NUMBER THAT SHALL COMPLY WITH THIS
 REQUIREMENT.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE ROOM IN
 QUESTION HAS NOT BEEN INDICATED ON THE
 MATRIX.
  
 13. SHT A.17 BREAK SINK TO COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT NO DETAIL FOR
 THE SINK IS LOCATED ON SHT A.17.
  
 14. SHT A.17 PLAN KEY NOTES: SHOW THE
 LOCATIONS OF NUMBER 2 & 10. SECTION
 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT DO NOT
 UNDERSTAND THE RESPONSE. KEY NOTES HAVE
 BEEN DELETED, AND THE EYE WASH AND THE
 ICE MACHINE AS INDICATED PREVIOUSLY ARE
 NOT SHOWN. PLEASE CLARIFY.
  
 17. SHT A.34 PUBLIC TOILETS, PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SECTION 106.1.1.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS NOT SHOWN:
 FOR THE UNINAL:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.4 FLUSH CONTROLS
 FOR THE LAV'S:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.5 FAUCETS.
  
 32. P-15 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLAN APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT THERE ARE SOME
 CUT SECTIONS THAT DO NOT SHOW THE
 LENGTH.
 ****RESPONSE NOTED, BUT THERE IS NO
 LENGTHS FOR THE PIPING TO THE POOL/SPA
 HEATERS. THERE ARE 3 WATER HEATERS
 INDICATED, BUT ONLY TWO SHOWN ON THE
 ISOMETRIC RISER DIAGRAM. PLEASE
 CORRELATE THE APPLIANCES WITH THE RISER
 DIAGRAM.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NOT ADDRESSED.
 ****RESPONSE NOTED, BUT MANUF.
 SPECIFICATION SHEET ARE REQUIRED FOR ALL
 GAS APPLIANCES.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. BYPASS
 PIPING SHALL BE CONNECTED DOWNSTREAM OF
 THE EMERGENCY HOOD SHUT OFF VALVE.
 ***NO RESPONSE, NOT ADDRESSED. EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" PER
 NFPA-96 SECTION 10.5.1 AND NFPA-1
 SECTION 50.4.7.1. INDICATE ON GAS RISER.
 ****RESPONSE NOTED, BUT NO MANUAL GAS
 SHUT OFF VALVE IS SHOWN ON RISER
 DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 RESUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved